2 – Roof
2.2.1 – Roof Covering
Roof Covering 1
Roof Covering 2
DAMAGED/DETERIORATED

The roof covering material was damaged/deteriorated in some areas.  A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.2.2 – Roof Covering
Roof Covering 3
Roof Covering 4
EXPOSED NAILS

The inspector observed exposed nails on the roof covering. This condition could allow moisture to penetrate the roof component. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.6.1 – Flue Gas Vent Pipes
Flue Gas Vent Pipes 1
INADEQUATE CLEARANCE – ROOF

One or more combustion appliance exhaust flue(s) did not extend far enough above the roof. To ensure proper and safe operation, exhaust flues should extend at least 3 feet above the roof, and 2 feet above any portion of the roof within 10 feet (measured horizontally).  A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.7.1 – Roof Drainage Systems
Roof Drainage Systems 1
BENT/DAMAGED

Gutters were bent and/or damaged at the time of the inspection.

This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

3 – Attic, Insulation and Ventilation
3.4.1 – Insulation in Attic
NOT UNIFORM

The insulation is not uniform: thicker in areas, thinner in areas, or possibly missing in some areas.

Recommend a qualified contractor evaluate and repair or replace as needed.

3.4.2 – Insulation in Attic
Insulation in Attic 1
TOO THIN

The insulation is thinner than current thermal resistance (R-value) standards.

Recommend a qualified contractor evaluate and repair or replace as needed.

4 – Exterior
4.2.1 – Driveways
Driveways 1
CRACKING – MODERATE

The concrete driveway was moderately cracked. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.

4.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
Wall-Covering, Flashing & Trim 2
DAMAGED – SIDING

The siding and/or trim was damaged in areas of the exterior.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.4.2 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
Wall-Covering, Flashing & Trim 2
SEAL GAPS AT INTERSECTIONS
MULTIPLE AREAS

Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.

4.4.3 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 3
Wall-Covering, Flashing & Trim 4
WOOD ROT

The siding and/or trim appeared to be rotted in areas. Recommend a qualified contractor evaluate and repair or replace as necessary.

4.11.1 – Walkways
Walkways 1
Walkways 2
CRACKING – MODERATE

There were signs of moderate cracking on the walkway(s) in areas. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.

4.11.2 – Walkways
Walkways 3
HEAVING AND/OR SETTLING

The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose or it can no longer support the weight causing it to sink or crack.

  • This causes cracks in the concrete.
  • This creates trip hazards that could result in injury.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
LARGE TREES FOUNDATION

Consideration should be given to trimming or even removing large tree(s) located close to the structure. We suggest consultation with a tree specialist. Evaluating trees lies beyond the scope of the general property inspection.

Recommend a qualified contractor evaluate and repair or replace as necessary.

4.12.2 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 2
Vegetation, Grading & Drainage 3
NEGATIVE GRADING

The property had areas of neutral or negative drainage, which will route runoff from precipitation to the foundation.  Excessive moisture content in soil supporting the foundation can cause foundation and other structural damage from undermining, heaving or settling, depending on soil composition, moisture content and other conditions.The ground around the property should slope away from all sides, ideally 6 inches for the first 10 feet from the house foundation perimeter. Downspouts, surface gutters and drains should also be directing water away from the foundation. A qualified contractor should evaluate and repair as necessary according to current standards.

4.12.3 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 4
VINES ON SIDING

Vegetation growing on siding should be removed and kept away from eaves, woodwork, doors, chimneys, or other building components. They hold moisture against the wall, hide rot and other problems and are conducive conditions for termites, carpenter ants,  etc. The growth does not allow full inspection of the siding and can hide potential defects underneath.

Recommend a qualified contractor evaluate and repair or replace as necessary.

4.14.1 – Exterior Faucets (Hose Bibs)
Exterior Faucets (Hose Bibs)
LOOSE IN WALL

One or more exterior faucet was loose in the wall. The faucet should be securely fastened to the wall using appropriate screws depending on the material at the location of the faucet. Recommend a qualified contractor evaluate and repair or replace as needed.

4.17.1 – Exterior Foundation Wall
Exterior Foundation Wall 1
CRACK – VERTICAL

The foundation had vertical cracks in areas. A qualified contractor should evaluate and repair as necessary before your inspection objection deadline.

4.18.1 – Exterior Vents
Exterior Vents 1
DAMAGED VENT COVER
One or more vent covers were damaged. A damaged vent assembly can allow entry of water, air, or rodents into vent ducts or home. A qualified contractor should evaluate and repair or replace as necessary.
4.21.1 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 1
MISSING – EXTENSIONS

Downspout(s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

5 – Attached Garage
5.2.1 – Occupant Door
Occupant Door 1
NOT FIRE RATED

The inspector was unable to verify that the door was fire rated . This may be considered a fire safety hazard. The door between the garage and the house should be a solid wood door at least 1-3/8 inches thick, a solid or honeycomb-core steel door at least 1-3/8 inches thick, or a 20-minute fire-rated door. This means that should a fire occur in garage, the occupant door does not afford protection until firemen arrive. A qualified contractor should evaluate and repair or replace as necessary.

5.2.2 – Occupant Door
Occupant Door 2
NOT SELF CLOSING

The door between the garage and the living space failed to close by itself. Modern safety requirements require that the door between the home interior and the garage be self-closing for safety reasons related to fire hazard and toxic fumes. A qualified contractor should evaluate and repair or replace as necessary.

5.3.1 – Ceiling, Walls & Firewalls
Ceiling, Walls & Firewalls 1
SIGNS OF REPAIRS

Walls and/or ceilings had signs of repairs at the time of inspection. Recommend asking current home owners for more information. Should repairs appear to be poorly done, we recommend having a qualified contractor evaluate further for any further repairs.

5.4.1 – Floor
Floor 1
CRACKING – MODERATE

The concrete floor in the garage was moderately cracked. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.

5.6.1 – Door Opener
Door Opener 1
REVERSE SENSORS TOO HIGH

The photo-electric reverse sensors are installed too high from the garage floor surface.

The vertical distance between the photo-eye beam and the floor should be no more than 6 inches.

5.7.1 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 1
NO GFCI PROTECTION

The garage had one or more outlets without GFCI (or ground fault circuit interrupter) protection.

GFCI protection is required for all 15- and 20-amp receptacles, including outlets for refrigerators, sprinkler systems, garage door openers, and washing machines – some items may not be protected on purpose due to the potential for them to go unnoticed and cause damage. A qualified contractor should evaluate and repair or replace as necessary.

5.7.2 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 2
SPRINKLER SYSTEM MAKING BUZZING NOISE.
6 – Interior, Doors, Windows
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
SIGNS OF REPAIR-CEILINGS

The interior ceilings have signs of repairs. Recommend asking the current homeowner for more information. Recommend further evaluation from a qualified contractor should the repairs be excessive or of visibly poor quality.

6.3.1 – Floors
Floors 1
DAMAGED – FLOOR COVERING

There appeared to be some damage to the interior flooring in areas. Recommend a qualified contractor evaluate and repair or replace as needed.

6.5.1 – Windows
Windows 1
LOCK DAMAGED/MISSING
The window had damaged or missing lock hardware.  A qualified contractor should evaluate and repair or replace as necessary.
6.5.2 – Windows
Windows 2
Windows 3
SCREENS DAMAGED/MISSING

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

6.6.1 – Electrical Outlets
Electrical Outlets 1
Electrical Outlets 2
NOT GROUNDED – OUTLET
One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.
6.8.1 – Stairways & Railings
Stairways & Railings 1
LOOSE – STEPS
At the interior stairs the steps were loose and not properly secured.  A qualified contractor should evaluate and repair or replace as necessary.
6.9.1 – Smoke & CO Detectors
Smoke & CO Detectors 1
CO DETECTOR >15 FEET

Carbon monoxide detectors were installed greater than 15 feet of rooms used for sleeping purposes. The inspector recommends installation of carbon monoxide detectors in appropriate locations. Colorado House bill 1091 became effective on July 1, 2009 that requires Carbon Monoxide detectors to be installed in most properties that has a fuel-burning heater or appliance, a fireplace, or an attached garage within a specified distance of each room lawfully used for sleeping purposes.

6.9.2 – Smoke & CO Detectors
Smoke & CO Detectors 2
SMOKE DETECTOR MISSING

The smoke detector was missing. A qualified person should replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.

6.10.1 – Installed Heat Source
Installed Heat Source 1
LOOSE, DAMAGED – REGISTER COVER

The supply register cover was loose or damaged.  A qualified contractor should evaluate and repair or replace as necessary.

7 – Kitchen
7.5.1 – Cabinets & Counters
Cabinets & Counters 1
DAMAGED – CABINET FLOOR

The cabinet floor was damaged. This may be from excessive leaking pipes, condensation, or even leaking cleaners stored in cabinet over the years.

A qualified contractor should evaluate and repair or replace as necessary.

7.5.2 – Cabinets & Counters
Cabinets & Counters 2
POSSIBLE MOLD

Evidence of a possible mold like substance was observed.  We did not inspect, test or determine if this growth is or is not a health hazard. The underlying cause is moisture. It is recommended to consult a mold inspector or mold remediation specialist to determine if further action is needed. Further analysis by a mold remediation specialist is recommended. Axium recommends our premier partner – Mold Removal Express. They can be contacted at 720-464-1555

7.6.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION

No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

7.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
SLOPE INCORRECT

The sink drain pipe appeared to slope the wrong direction. The drain line should have a slight slope away from the fixture to allow for proper draining and to prevent water and debris from resting inside the pipe.  A qualified contractor should evaluate and repair or replace as necessary.

7.10.2 – Drain Waste and Vent System
Drain Waste and Vent System 1
DAMAGED
7.15.1 – Range Hood
Range Hood 1
NOT WORKING

The exhaust vent fan was not operational at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

8 – Laundry
8.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION NOT PRESENT

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

9 – Bathroom
9.7.1 – Electrical Outlets
Electrical Outlets 2
NO GFCI PROTECTION

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time of in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

9.7.2 – Electrical Outlets
Electrical Outlets 3
NOT GROUNDED – GFCI OUTLET

A GFCI outlet was not grounded and did not trip when tested. A GFCI requires a ground wire to route electricity when tripped. A qualified contractor should evaluate and repair or replace as necessary.

9.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
NOT WORKING – SINK STOPPER

The drain stop did not work or did not hold water in the sink.  A qualified contractor should evaluate and repair or replace as necessary.

9.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
LEAK – SHOWER HEAD

There was a leak at the shower head connection at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.

9.13.1 – Toilets
Toilets 1
LOOSE AT THE FLOOR

The toilet was loose at the floor. This condition typically is caused by loose bolts or nuts and/or missing floor seals. Loose toilet can result in leaks, water damage, and mold, as well as damage to the toilet, water supply lines, bolts, and drainage pipes. A qualified contractor should evaluate and repair or replace as necessary.

9.13.2 – Toilets
Toilets 2
RUNS AFTER FLUSHING

The toilet continually “runs” after flushing. This generally means the interior tank components are not working properly. A qualified contractor should evaluate and repair or replace as necessary.

9.14.1 – Tub, Shower Area
Tub, Shower Area 1
CAULK – CORNERS AND FLOOR

The tub/shower area had deteriorated or missing sealant (caulking or grout) at the corners and/or floor. Sealant is needed at wall corners inside the shower, corners from tub to wall, and along the floor perimeter.  A qualified contractor should evaluate and repair or replace as necessary.

9.14.2 – Tub, Shower Area
Tub, Shower Area 2
CHIPPED – TUB

The bathtub finish was chipped or damaged.  A qualified contractor should evaluate and repair or replace as necessary.

11 – Electrical
11.2.1 – Distribution Panels
Distribution Panels 1
INADEQUATE WORKSPACE – PANEL

The distribution panel had inadequate clear space that is 3 feet deep, 30 inches wide, and 6′ 6″ in height in front of the equipment. A qualified contractor should evaluate and repair or replace as necessary.

12 – Water Heating Equipment
12.6.1 – Combustion Air Supply
Combustion Air Supply 1
NOT PRESENT

The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.

Fresh air supply is recommended by manufacturers for efficient operation of fuel burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.

12.8.1 – Temperature & Pressure Relief Valve
Temperature & Pressure Relief Valve 1
IMPROPER MATERIAL

An improper material was used for the TPR pipe. The pipe should be a heat rated material. A qualified contractor should evaluate and repair or replace as necessary.

13 – Heating
13.1.1 – Heating System Information
Heating System Information 1
BEYOND TYPICAL LIFE EXPECTANCY

Due to the year of manufacture, the heating system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.  InterNACHI’s Standard Estimate Life Expectancy Chart for Homes

13.3.1 – Combustion Air Supply
NOT PRESENT

The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.

Fresh air supply is recommended by manufacturers for efficient operation of fuel burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.

13.4.1 – Shut-Off Switch
Shut-Off Switch 1
DAMAGED FACEPLATE

The shut-off switch faceplate was damaged at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as needed.

13.5.1 – Gas Supply Shut-Off Valve
Gas Supply Shut-Off Valve 1
NO FLEX LINE

The gas supply line lacked a flex hose to allow for movement of the concrete slab. A qualified contractor should evaluate then repair or replace as advised.

13.8.1 – Ductwork
Ductwork 1
DUCT DAMAGED

The ductwork was damaged. A qualified contractor should evaluate and repair or replace as necessary.

13.8.2 – Ductwork
Ductwork 2
DUCTS NOT SEALED

Air supply ducts were not sealed. Ideally all ducts are sealed with mastic in order to be more energy-efficient. A qualified contractor should evaluate and repair as necessary.

13.10.1 – Blower
Blower 1
BLOWER, CABINET DIRTY

The blower motor, wheel, and/or cabinet appeared to be dirty at the time of inspection. Blower fans/wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.

A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.

14 – Cooling
14.1.1 – Cooling System Information
Cooling System Information 1
BEYOND TYPICAL LIFE EXPECTANCY
Due to the year of manufacture, the cooling system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.  InterNACHI’s Standard Estimated Life Expectancy Chart for Homes
14.3.1 – AC Compressor
AC Compressor 1
CLEAN/SERVICE

Due to the current conditions at the time of inspection, the air conditioner is recommended to be cleaned, evaluated, and serviced by a qualified contractor. Consult with your real estate agent for your available options prior to closing.

14.3.2 – AC Compressor
AC Compressor 2
DAMAGED COMPONENTS
14.3.3 – AC Compressor
AC Compressor 3
LEAKING
15 – Structural Crawlspace
15.3.1 – Moisture Intrusion
ACTIVE LEAK

The inspector observed signs of a possible active leak in the crawlspace.

15.3.2 – Moisture Intrusion
Moisture Intrusion 1
EFFLORESCENCE

Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, a water proofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.

15.3.3 – Moisture Intrusion
MOISTURE INTRUSION

There were water stains or water damaged areas in the crawlspace at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.

15.3.4 – Moisture Intrusion
Moisture Intrusion 2
POSSIBLE MOLD

Evidence of a possible mold like substance was observed.  We did not inspect, test or determine if this growth is or is not a health hazard. The underlying cause is moisture. It is recommended to consult a mold inspector or mold remediation specialist to determine if further action is needed. Further analysis by a mold remediation specialist is recommended. Axium recommends our premier partner – Mold Removal Express. They can be contacted at 720-464-1555

15.3.5 – Moisture Intrusion
Moisture Intrusion 3
Moisture Intrusion 4
Moisture Intrusion 4
WATER DAMAGE AROUND PLUMBING

Water damage was visible in the crawlspace floor structure around plumbing lines. There may be a past or current leak in the nearby drain or supply lines that could further stain or rot wood if not corrected.

15.5.1 – Foundation Wall
Foundation Wall 1
Foundation Wall 2
MINOR CRACKS

There were several cracks in the crawlspace foundation wall. These cracks should be sealed to prevent moisture intrusion, and monitored for further movement. Further analysis by a licensed structural engineer is recommended. Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540

15.8.1 – Electrical in Crawlspace
Electrical in Crawlspace 1
JUNCTION BOX MISSING COVER PLATE

Splice/Junction box was missing a cover plate. A qualified contractor should evaluate and repair or replace as necessary.

15.9.1 – Plumbing in Crawlspace
Plumbing in Crawlspace 1
LEAKING – DRAIN PIPES
Drain pipes in the crawlspace were leaking in areas at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.