3 – Attic, Insulation and Ventilation
3.4.1 – Insulation in Attic
Insulation in Attic 1
TOO THIN
The insulation is thinner than current thermal resistance (R-value) standards.

Recommend a qualified contractor evaluate and repair or replace as needed.

4 – Attic, Insulation and Ventilation 2
4.1.1 – Attic Access
Attic Access 1
DAMAGED HATCH
The attic access hatch was damaged. A qualified contractor should evaluate and repair or replace as necessary.
4.1.2 – Attic Access
Attic Access 2
WIRE ACROSS HATCH
Your wire was running across the attic access hatch at the time of inspection. This Is an access restriction, and is a potential electrical hazard. Recommend a qualified contractor evaluate and reposition the electrical wire as needed.
4.4.1 – Insulation in Attic
Insulation in Attic 1
COMPRESSED – INSULATION
The insulation had been walked on or had stored items compressing it, which reduces the R-value.

Recommend a qualified contractor evaluate and repair or replace as needed.

4.4.2 – Insulation in Attic
Insulation in Attic 2
TOO THIN
The insulation is thinner than current thermal resistance (R-value) standards.

Recommend a qualified contractor evaluate and repair or replace as needed.

5 – Exterior
5.6.1 – Exterior Doors
Exterior Doors 1
DAMAGE – SCREEN DOOR
POOL AREA

The screen door was damaged or deteriorated at the time of inspection.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

5.6.2 – Exterior Doors
Exterior Doors 2
DIFFICULT TO SLIDE
PRIMARY BEDROOM

The sliding glass or screen door did not operate properly. The door(s) were operated and did not slide smoothly on the track and/or close using normal operating force.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

5.11.1 – Walkways
Walkways 1
DETERIORATED
BACK PATIO

The walkway(s) were deteriorated or was eroded in areas. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

5.22.1 – Additional Structures
Additional Structures 1
NEGATIVE GRADING
BARN

The back right corner of the barn had negative grading. This condition could allow moisture to enter into the barn. Recommend having a qualified contractor evaluate and repair or replace as necessary.

5.22.2 – Additional Structures
Additional Structures 2
MOISTURE STAINS
BARN

The wood frame area around the skylights had moisture stains. Recommend having a qualified contractor evaluate and repair or replace as necessary.

5.22.3 – Additional Structures
Additional Structures 3
FAUCET LEAKS
BARN

The faucet inside the barn when the handle was in the “up” position with a pressure gauge attached. Recommend having a qualified contractor evaluate and repair or replace as necessary.

6 – Detached Garage
6.4.1 – Ceiling & Walls in Garage
Ceiling & Walls in Garage 1
MOISTURE INTRUSION
Garage walls/ceilings showed signs of moisture intrusion. Recommend a qualified contractor evaluate and find source of moisture to prevent further damage and/or mold.
6.5.1 – Floor
Floor 1
CRACKED – COMMON
The concrete floor in the garage was cracked.

A qualified contractor should evaluate and repair as necessary.

6.9.1 – Door Opener 2
Door Opener 2 1
REVERSE SENSORS TOO HIGH
The photo-electric reverse sensors are installed too high from the garage floor surface.

The vertical distance between the photo-eye beam and the floor should be no more than 6 inches.

6.10.1 – Interior Outlets & Fixtures
Interior Outlets & Fixtures 1
NO GFCI PROTECTION
The garage had one or more outlets without GFCI (or ground fault circuit interrupter) protection.

GFCI protection is required for all 15- and 20-amp receptacles in a garage, including outlets for refrigerators, sprinkler systems, garage door openers, and washing machines – some items may not be protected on purpose due to the potential for them to go unnoticed and cause damage. A qualified contractor should evaluate and repair or replace as necessary.

7 – Interior, Doors, Windows
7.2.1 – Ceilings & Walls
Ceilings & Walls 1
DAMAGED – CEILINGS
PRIMARY

The ceilings showed signs of minor damage and wear.  A qualified contractor should evaluate and repair or replace as necessary.

7.3.1 – Floors
Floors 1
WEAR AND TEAR
The floors showed signs of minor damage and wear, particularly in high-traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.
7.7.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
FAN NOISY
PRIMARY

The ceiling fan was noisy when on.  A qualified contractor should evaluate and repair or replace as necessary.

7.13.1 – Fireplace Wood-Burning Primary
Fireplace Wood-Burning Primary 1
CLEANING NEEDED

The visible areas of the firebox and chimney flue were dirty at the time of the inspection. Most of the chimney flue was inaccessible and was not inspected. Dirty flues are potential fire hazards and should be cleaned by a professional. Recommend having the chimney evaluated by a C.S.I. (Chimney Safety Institute) -qualified chimney sweep.

8 – Kitchen
8.4.1 – Floors
Floors 1
MISSING/DAMAGED GROUT
The tile floor had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.
8.6.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION
No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

8.7.1 – Windows
Windows 1
SCREENS DAMAGED/MISSING

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

8.9.1 – Faucets Fixtures
Faucets Fixtures 1
FAUCET LEAKED

The sink faucet leaked.  A qualified contractor should evaluate and repair or replace as necessary.

8.15.1 – Range Hood
Range Hood 1
NOT PRESENT
There was not a range hood vent installed in the kitchen at the time of inspection. A kitchen exhaust fan is recommended to remove grease, smoke, and fumes that are present in the air when cooking in your oven or on your stovetop.

Recommend a qualified contractor evaluate and install kitchen exhaust as necessary.

10 – Laundry
10.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION NOT PRESENT

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

11 – Bathroom
11.7.1 – Electrical Outlets
Electrical Outlets 2
WIRED TO LIGHT

An electrical outlet was wired to a light fixture and is not separate.  A qualified contractor should evaluate and repair or replace as necessary.

11.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
DAMAGE – FAUCET FINISH

The finish on the faucet is damaged.  A qualified contractor should evaluate and repair or replace as necessary.

11.14.1 – Tub, Shower Area
Tub, Shower Area 1
Tub, Shower Area 2
Tub, Shower Area 3
MISSING/DAMAGED GROUT
Tiles on the wall in the bath/shower area had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.
12 – Bathroom Upstairs
12.5.1 – Floors
Floors 1
MISSING/DAMAGED GROUT
The tile floor had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.
12.7.1 – Electrical Outlets
Electrical Outlets 1
DID NOT TRIP – GFCI OUTLET

A GFCI outlet was defective (did not trip when tested). A qualified contractor should evaluate and repair or replace as necessary.

12.9.1 – Cabinets & Counters
Cabinets & Counters 1
Cabinets & Counters 2
GROUT – BACKSPLASH/WALL

The tile on the wall or backsplash had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.

12.9.2 – Cabinets & Counters
Cabinets & Counters 3
WATER STAINS
There appeared to be a stain in the base of the cabinet.
12.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
EVIDENCE OF LEAKING.
12.14.1 – Tub, Shower Area
Tub, Shower Area 1
MISSING/DAMAGED GROUT

Tiles on the wall in the bath/shower area had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.

13 – Bathroom 1st floor shared
13.5.1 – Floors
Floors 1
MISSING/DAMAGED GROUT

The tile floor had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.

13.6.1 – Windows
Windows 1
BROKEN SEALS

The window appeared to have a broken seal that has been compromised.  Condensation and/or cloudiness between the two panes of glass was observed.  This will have a negative impact on energy efficiency.  Also, because there is moisture between the panes with no ventilation, mold can eventually develop.  A qualified contractor should evaluate and repair or replace as necessary.

13.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
CRACKED/DAMAGED – SINK

The sink was cracked or damaged.  A qualified contractor should evaluate and repair or replace as necessary.

13.13.1 – Toilets
Toilets 1
INADEQUATE CLEARANCE

The toilet had inadequate clearance.  There should be 21 inches of clearance in front of the toilet and 15 inches of clearance measured from the center of the toilet to the sides. A qualified contractor should evaluate and repair or replace as necessary.

14 – Bathroom 1/2 main level
14.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
LEAK – SINK CONTROL VALVE

A control valve at the sink was leaking during operation at the time of inspection.

A qualified contractor should evaluate and repair or replace as necessary.

17 – Plumbing
17.4.1 – Water Pressure
Water Pressure 1
HIGH WATER PRESSURE

The property water supply pressure  measured at the exterior faucet or laundry appliance hose bib. Property water supply pressure exceeded the 80 pounds per square inch (PSI) limit considered the maximum allowable by generally accepted current standards. Excessively high water pressure can stress connections in the plumbing system and appliances is likely to cause leaks.

A qualified contractor should install a pressure regulator or evaluate and repair or replace one as necessary.

17.8.1 – Pool Equipment
Pool Equipment 1
Pool Equipment 1
LEAKING
The floor surrounding the pool equipment was wet and had water staining indicating a leak could be possible. Recommend having a pool specialist evaluate the system and repair or replace as necessary.
18 – Electrical
18.2.1 – Distribution Panels

Distribution Panels 1

MISSING – CIRCUIT LABELS
OUTSIDE MAIN PANEL

The circuit labels were missing, partial, or illegible at the electrical distribution panel. The circuit labels provide information describing the locations each individual circuit breaker provides power too.

Recommend a qualified contractor verify the breakers and accuracy of any existing labeling as necessary.

18.2.2 – Distribution Panels
Distribution Panels 2
Distribution Panels 3
OPEN GAPS – PANEL
OUTSIDE MAIN PANEL

Gaps were present at the electrical panel were the cover was protruding outwards from the panel. An object or finger could fit through the gap and create a shock hazard. A qualified contractor should evaluate and repair and replace as necessary.

18.5.1 – Electrical Circuit Breakers
Electrical Circuit Breakers 1
DIFFERENT BRANDS

Some or all circuit breakers were a brand different from the main panel brand. Circuit breakers made by different manufacturers vary in design, therefore panel manufacturers require their own manufactured breakers to be used. Select brands are interchangeable, and there are some “semi” universal breaker types or panel types.

Using incompatible breakers in the panel of another manufacturer may result in poor connections which can create a potential fire or shock/electrocution hazard. A qualified contractor should evaluate and repair or replace as necessary.

19 – Electrical 2
19.2.1 – Distribution Panels
Distribution Panels 1
OPEN KNOCKOUT – BREAKER
PANEL IN BASEMENT

Unused circuit-breaker panel opening was missing filler plate. A qualified contractor should evaluate and repair and replace as necessary.

19.2.2 – Distribution Panels
Distribution Panels 2
SCREWS MISSING – PANEL COVER
BASEMENT SUB PANEL

Screws / fasteners were missing at the electrical panel cover. A qualified contractor should evaluate and repair or replace as necessary.

19.6.1 – Electrical Circuit Breakers
Electrical Circuit Breakers 1
DIFFERENT BRANDS
PANEL IN BASEMENT

Some or all circuit breakers were a brand different from the main panel brand. Circuit breakers made by different manufacturers vary in design, therefore panel manufacturers require their own manufactured breakers to be used. Select brands are interchangeable, and there are some “semi” universal breaker types or panel types.

Using incompatible breakers in the panel of another manufacturer may result in poor connections which can create a potential fire or shock/electrocution hazard. A qualified contractor should evaluate and repair or replace as necessary.

19.6.2 – Electrical Circuit Breakers
Electrical Circuit Breakers 2
DOUBLE TAP
BASEMENT SUB PANEL

One or more circuit breakers have two wires that are connected to a breaker designed for only one wire. This is known as a “double-tap” and is a defective condition. A qualified contractor should evaluate and repair or replace as necessary.

20 – Water Heating Equipment
20.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE HIGH
The water temperature was higher than the acceptable range of 120-130 degrees. We recommend adjusting the water heater thermostat.
22 – Heating 2
22.6.1 – Cabinet
Cabinet 1
Cabinet 2
CORRODED, RUSTED
The heating system cabinet and pipe connections were corroded, rusted or damaged in some areas. A qualified contractor should evaluate and repair or replace as necessary.
22.13.1 – TPR Valve
TPR Valve 1
TPR Valve 2
LEAKING

The temperature pressure relief valve was leaking at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.

25 – Structural Basement
25.9.1 – Electrical in Basement
Electrical in Basement 1
EXPOSED ELECTRICAL SPLICES

Exposed electrical conductor splices need to be installed inside a junction box with cover plate. A qualified contractor should evaluate and repair or replace as necessary.