1375 N Williams St unit 102
Denver, CO 80218
There was cracking around some windows on the interior (where the window meets the wall). A qualified contractor should evaluate and repair or replace as necessary.
Accent trim was damaged at areas of the interior walls at the time of inspection.
Recommend a qualified contractor evaluate and repair or replace as needed.
Minor cracking was visible on the interior walls. A qualified contractor should evaluate and repair or replace as necessary.
The interior walls have signs of repairs, including possibly repaired minor cracks.
Recommend asking the current homeowner for more information. Recommend further evaluation from a qualified contractor should the repairs be excessive or of visibly poor quality.
The tile floor had missing or damaged grout. A qualified contractor should evaluate and repair or replace as necessary.
The floors showed signs of minor damage and wear, particularly in high-traffic areas. A qualified contractor should evaluate and repair or replace as necessary.
The interior floor covering has signs of repairs. Recommend asking the current homeowner for more information. Recommend further evaluation from a qualified contractor should the repairs be excessive or of visibly poor quality.
The door surface was damaged. A qualified contractor should evaluate and repair or replace as necessary.
The window had damaged or missing lock hardware. A qualified contractor should evaluate and repair or replace as necessary.
Windows installed in the home appeared to be worn or aged. This apparent condition can mean the windows are deteriorated or difficult to operate, and can also mean they are not consistent with current efficiency standards. They were possibly original and were either at or near their serviceable lifespan. Recommend further evaluation by a qualified contractor and budgeting for potential future replacement.
Some windows had damaged or missing screens. A qualified contractor should evaluate and repair or replace as necessary.
One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.
Carbon monoxide detectors were not installed within a specified distance of each room lawfully used for sleeping purposes. The inspector recommends installation of carbon monoxide detectors in appropriate locations. Colorado House bill 1091 became effective on July 1, 2009 that requires Carbon Monoxide detectors to be installed in most properties that has a fuel-burning heater or appliance, a fireplace, or an attached garage.
There are no carbon monoxide detectors on the lower or upper level.
The smoke detector was missing. A qualified person should replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.
The doors in the kitchen area were missing. A qualified contractor should evaluate and repair or replace as necessary.
The ceilings showed evidence that moisture was entering from behind possibly including damage and deterioration. A qualified contractor should evaluate and repair or replace as necessary.
The tile floor was cracked/damaged. A qualified contractor should evaluate and repair or replace as necessary.
The tile backsplash had missing or damaged grout. A qualified contractor should evaluate and repair or replace as necessary.
No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:
1. Replacing the current standard outlets with GFCI outlets.
2. Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet
3. Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.
A qualified contractor should evaluate and repair or replace as necessary.
The sink faucet leaked. A qualified contractor should evaluate and repair or replace as necessary.
The sink drain pipe was leaking at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.
The food waste disposer had exposed or improper wiring. A qualified contractor should evaluate and repair or replace as necessary.
The oven was difficult to ignite. The bake function only lit after the broil function was turned on first. No gas leaks were detected at the time of inspection at the gas shut off valve. Recommend having a qualified contractor evaluate and repair or replace as necessary.
An interior door rubs at the door frame when closing. This may mean the door or frame is out of square or that hinges may not be installed properly.
A qualified contractor should evaluate and repair or replace as necessary.
The tile floor was cracked/damaged. A qualified contractor should evaluate and repair or replace as necessary.
The tile floor had missing or damaged grout. A qualified contractor should evaluate and repair or replace as necessary.
Loose tiles are present at time of inspection. Recommend a qualified contractor repair or replace as necessary.
The sink drain pipe was leaking at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.
The water supply valves and supply lines at the sink fixture in the bathroom were installed improperly with a reversed configuration. Current standards for installation produce hot water when the valve is turned to the left and cold water when the valve is turned to the right. A qualified contractor should evaluate and repair or replace as necessary.
The water distribution supply pipe was corroded in one or more areas. The distribution piping runs from the main source to each faucet or fixture.
A qualified contractor should evaluate and repair or replace as necessary.
The property contained galvanized steel water distribution pipes. These pipes are outdated and subject to corrosion which will eventually result in restricted flow and leakage and will need to be replaced. Water flow in the property was satisfactory at the time of the inspection.