4 – Exterior – Condo/Townhome
4.1.1 – Exterior Doors
Exterior Doors1
DAMAGED – HARDWARE
BACK

Damage to the hardware and/or latch

was present the fence gate.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.1.2 – Exterior Doors
Exterior Doors 2
LOOSE/DAMAGE – WEATHER STRIPPING
FRONT

An entry door had damaged or loose weather stripping at the time of the inspection. A qualified contractor should evaluate and repair or replace as necessary.

4.2.1 – Exterior Vents
Exterior Vents 1
DAMAGED VENT COVER

One or more vent covers were damaged. A damaged vent assembly can allow entry of water, air, or rodents into vent ducts or home. A qualified contractor should evaluate and repair or replace as necessary.

 6 – Interior, Doors, Windows
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
ASBESTOS CEILING

The property had ceiling materials that may contain asbestos. Ceiling tiles or popcorn texture were manufactured or installed using asbestos as late as the early 90s.

In the past, asbestos fibers were added during the production to strengthen and increase durability. Materials that contain asbestos, when intact and in good condition, is generally considered non-friable and is not hazardous. Heat, water, weathering or aging can weaken asbestos materials to the point where it is considered friable. Friable material includes any material containing more than 1 percent asbestos that can be crumbled, pulverized or reduced to powder with hand pressure. This includes previously non-friable material which has been damaged to the extent that it may be crumbled, pulverized or reduced to powder by hand pressure and can also be made friable during its removal. Friable materials can release asbestos fibers into the air. Once in the air, asbestos fibers present a health hazard to people who inhale those fibers.

6.2.2 – Ceilings & Walls

Ceilings & Walls 2

Ceilings & Walls 3

Ceilings & Walls 4

DAMAGED – MULTIPLE ITEMS
MULTIPLE AREAS THROUGHOUT PROPERTY

The ceiling and/or walls showed various signs of minor defects at numerous locations including all or some of the following: damage, cracks, holes, previous repairs, and/or improper repairs. A representative number of pictures were taken to provide an example. Should any of these issues appear excessive we recommend a qualified contractor should evaluate and repair or replace items as necessary.

6.3.1 – Floors
Floors 1
Floors 2
CRACKED/DAMAGED TILE
FRONT ENTRY

The tile floor was cracked/damaged.  A qualified contractor should evaluate and repair or replace as necessary.

6.3.2 – Floors

Floors 3

Floors 4

Floors 5

DAMAGED – FLOOR COVERING

There appeared to be some damage to the interior flooring in areas. Recommend a qualified contractor evaluate and repair or replace as needed.

6.3.3 – Floors
FLOOR SQUEAKS
SEVERAL AREAS

The floor squeaks when stepped on in sever areas of the property. A qualified contractor should evaluate and repair or replace as necessary.

6.3.4 – Floors

Floors 1

NOT PROPERLY INSTALLED
COAT CLOSET

The flooring was not installed according to professional standards.  A qualified contractor should evaluate and repair or replace as necessary.

6.4.1 – Doors
Doors 1
WARPED DOOR
PRIMARY BEDROOM

The door or hinges were bent/warped at the time of inspection. This means the door needed a little extra force to close and latch. A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows
Windows 1
Windows 2
LOCK DAMAGED/MISSING
BASEMENT

The window had damaged or missing lock hardware.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.2 – Windows

Windows 3

NO EGRESS
BASEMENT

At the time of the inspection, the property did not have emergency escape and rescue openings which met generally-accepted current standards. Egress opening requirements:

For safety reasons, all sleeping room and basements greater than 200 square feet and new properties should meet the generally-accepted current standards for emergency escape and rescue openings, which include the following requirements:

1. Sill height shall not exceed 44 inches above the floor.

2. Minimum net clear opening shall be 5.7 square feet; exception – grade level windows

may have a minimum clear opening of 5 square feet.

3. Minimum net clear opening height shall be 24 inches.

4. Minimum net clear opening width shall be 20 inches.

6.7.1 – Electrical Fixtures & Switches

Electrical Fixtures & Switches 1

Electrical Fixtures & Switches 2

CHAIN MISSING/STUCK

Some light fixtures had a pull chain that was stuck or missing.  A qualified contractor should evaluate and repair or replace as necessary.

6.7.2 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 3
HANGS BY WIRE
GUEST BEDROOM CLOSET

The light fixture was hanging by the electrical wiring.  A qualified contractor should evaluate and repair or replace as necessary.

6.7.3 – Electrical Fixtures & Switches
FAN WOBBLES
GUEST BEDROOM

The ceiling fan wobbles when operated and may need to be balanced.  A qualified contractor should evaluate and repair or replace as necessary.

6.8.1 – Stairways & Railings
Stairways & Railings 1
MISSING – GUARDRAIL
STAIRWAY

At the interior stairs, the guardrail was missing.  A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

 7 – Kitchen
7.4.1 – Floors
Floors 1
Floors2
SEAMS WIDE/INCONSISTENT
KITCHEN

The flooring had seams that were wide or inconsistent possibly indication loose flooring or poor installation.  A qualified contractor should evaluate and repair or replace as necessary.

7.6.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION
KITCHEN

No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

7.12.1 – Food Waste Disposer
Food Waste Disposer 1
MISSING WIRING CLAMP

The food waste disposer was missing the wiring connector (clamp and bushing).  A qualified contractor should evaluate and repair or replace as necessary.

 8 – Laundry
8.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION NOT PRESENT
LAUNDRY AREA

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

8.9.2 – Electrical Outlets
OUTLET LOOSE CONTACTS
LAUNDRY AREA

An electrical outlet had loose contacts and no longer holds a plug securely. A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.5.1 – Floors
Floors 1
SEAMS WIDE/INCONSISTENT
UPSTAIRS BATHROOM

The flooring had seams that were wide or inconsistent possibly indication loose flooring or poor installation.  A qualified contractor should evaluate and repair or replace as necessary.

9.7.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION
UPSTAIRS BATHROOM

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time of in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

9.9.1 – Cabinets & Counters
Cabinets & Counters 1
LOOSE – HINGES
UPSTAIRS BATHROOM

Cabinet door hinges were loose at time of inspection. Recommend a qualified contractor evaluate and repair or replace as needed.

9.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
MISSING – SINK DRAIN STOPPER
UPSTAIRS BATHROOM

The sink drain stop was missing, damaged or did not operate properly.  A qualified contractor should evaluate and repair or replace as necessary.

9.12.1 – Plumbing Fixtures
LEAK – SHOWER HEAD
UPSTAIRS BATHROOM

There was a leak at the shower head connection at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.

9.12.2 – Plumbing Fixtures
WHISTLING

The supply line (behind the wall or at a fixture connection) whistled intermittently when more than one plumbing fixture was operated. Recommend a qualified contractor evaluate and repair or replace as needed.

Whistling or squealing water pipes generally results from water being forced through a smaller opening than the plumbing components were designed for. This is may be due to: water pressure too high, worn plumbing components, mineral build-up, or other issues that could only be discovered by dismantling the plumbing components.

9.12.3 – Plumbing Fixtures
Plumbing Fixtures 1
SHOWER HEAD REPLACENT
UPSTAIRS BATHROOM

The shower head and fixture were not installed and operating up to current standards and need replacement. A qualified contractor should evaluate and repair or replace as necessary.

 10 – Bathroom 2
10.2.1 – Doors
Doors 1
Doors 2
RUBS FRAME
1/2 BATHROOM

An interior door rubs at the door frame when closing. This may mean the door or frame is out of square or that hinges may not be installed properly.

A qualified contractor should evaluate and repair or replace as necessary.

10.7.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION
1/2 BATHROOM

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time of in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

10.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
FLEX PIPE
1/2 BATHROOM

Flexible drain lines can clog, leak or fail. Flex lines design includes multiple folds in which moisture may become trapped and mold may grow.  A qualified contractor should evaluate and repair or replace as necessary.

 11 – Plumbing
11.1.1 – Main Water Shut-Off Valve
NOT PRESENT – UNABLE TO BE DETERMINDED

The shut off valve was either not present or unable to be determined. It appears that multiple valves needed to be operated to turn off the water for the entire property. In the event of an emergency this could be problematic. A qualified contractor should evaluate, then repair or replace as advised.

 12 – Electrical
12.2.1 – Distribution Panels
Distribution Panels 1
MISSING – CIRCUIT LABELS

The circuit labels were missing, partial, or illegible at the electrical distribution panel. The circuit labels provide information describing the locations each individual circuit breaker provides power too.

Recommend a qualified contractor verify the breakers and accuracy of any existing labeling as necessary.

12.5.1 – Electrical Circuit Breakers
Electrical Circuit Breakers1
MISSING BREAKER CONNECTION

There were multiple “double-pull” breakers that were missing the connection pole to link them together. A qualified contractor should evaluate and repair or replace as necessary.

 13 – Water Heating Equipment
13.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE LOW

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

 14 – Heating
14.8.1 – Ductwork
Ductwork 1
Ductwork 2
Ductwork 3
DUCTS NOT SEALED/SECURED

Several air supply ducts were not sealed and/or secured to the vents. Ideally all ducts are sealed with mastic in order to be more energy-efficient and supply proper conditioned air to that specific areas. A qualified contractor should evaluate and repair as necessary.

14.12.1 – Heating System Ignition & Operation
SHORT CYCLING

The furnace was short-cycling (repeated start-up and shut-down within minutes of each other) at the time of the inspection. Most systems should run about 2-3 cycles per hour. A qualified contractor should evaluate and repair or replace as necessary.

 16 – Structural Basement
16.3.1 – Foundation Wall
Foundation Wall 1
Foundation Wall 2
Foundation Wall 3
MINOR CRACKS

There were minor to moderate cracks in the basement foundation wall. These cracks should be sealed to prevent moisture intrusion and monitored for further movement. Further analysis by a licensed structural engineer is recommended. Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540 or online at www.axiuminspections.com/structural-engineer.

16.5.1 – Moisture Intrusion
Moisture Intrusion 1
EFFLORESCENCE

Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, a water proofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.

16.7.1 – Insulation
NO INSULATION

There is no insulation on the basement exterior walls or floor system. Heat loss can occur more on this property than one that is properly insulated. A qualified contractor should evaluate and install as necessary.