2 – Roof
2.6.1 – Flue Gas Vent Pipes
Flue Gas Vent Pipes 1
CORRODED

One or more combustion appliance exhaust flue(s) exhibited heavy corrosion.  A qualified contractor should evaluate and repair/replace as necessary.

2.6.2 – Flue Gas Vent Pipes
Flue Gas Vent Pipes 2
INADEQUATE CLEARANCE – ROOF

One or more combustion appliance exhaust flue(s) did not extend far enough above the roof. To ensure proper draw, furnace flues should extend at least 3 feet above the roof, and 2 feet above any portion of the roof within 10 feet (measured horizontally). The correction could include the addition of a flue extension to encourage a proper draft.  A qualified contractor should evaluate and repair/replace as necessary.

2.7.1 – Masonry Chimney
Masonry Chimney 1
DAMAGE – MORTAR CROWN

The mortar crown was cracked or deteriorated at the time of inspection.

If the crown on top of the chimney is not properly sealed or is extensively cracked, defective, spalled, or displays rust stains, it should be replaced. Sheet metal caps/crowns with minor rust or corrosion should be repaired, but if rust or corrosion is extensive, replacement is recommended.

2.8.1 – Roof Drainage Systems
Roof Drainage Systems 1
Roof Drainage Systems 2
INCORRECT SLOPE

Gutters were noticeably flat or sloped “away from” the downspouts, which will prevent the water from being properly drained through the downspouts and away from the foundation.

This may even cause the water to overflow and cause damage to exterior walls and siding, or by introducing excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in the soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 3 – Attic, Insulation, and Ventilation
3.2.1 – Attic Structural Components
Attic Structural Components 1
Attic Structural Components 2
ROOF DECKING DAMAGED/ALTERED

The roof decking had been damaged or altered. This can affect the overall structural integrity of the roof, and cause the roof to sag or fail in that area.

Trusses are specifically engineered and designed to support the roof and loads placed on it, such as snow. The individual components of a truss — webs, connectors, gusset plates, straps, clips, and fasteners — and all trusses in a roof are designed to perform together as a system. Recommend further evaluation by a licensed roofing contractor and/or structural engineer to determine the effect of the damage or alterations, and options for any necessary repairs.

3.3.1 – Attic Moisture Intrusion
Attic Moisture Intrusion 1
WATER INTRUSION

Signs of previous water penetration or intrusion into the attic. Watermarks or stains were observed. Recommend asking the seller if there are any recent incidents that have been documented or mitigated.

Further evaluation is recommended.

3.3.2 – Attic Moisture Intrusion
Attic Moisture Intrusion 2
RUSTY NAILS

Rusty nails often signal excess condensation build-up due to poor ventilation. Recommend a qualified contractor evaluate further to repair or replace as needed.

3.4.1 – Insulation in Attic
Insulation in Attic 1
COMPRESSED – INSULATION

The insulation had been walked on or had stored items compressing it, which reduces the R-value.

Recommend a qualified contractor to evaluate and repair or replace as needed.

3.4.2 – Insulation in Attic
Insulation in Attic 2
TOO THIN

The insulation is thinner than current thermal resistance (R-value) standards.

Recommend a qualified contractor to evaluate and repair or replace as needed.

3.6.1 – Electrical Wiring In Attic
Electrical Wiring In Attic 1
JUNCTION BOX MISSING COVER PLATE

The splice/Junction box was missing a cover plate. A qualified contractor should evaluate and repair or replace as necessary.

 4 – Exterior
4.2.1 – Driveways
Driveways 1
HEAVING AND/OR SETTLING

The driveway showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose, or it can no longer support the weight causing it to sink or crack. This condition could potentially cause a trip hazard.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.10.1 – Window Wells
Window Wells 1
Window Wells 2WINDOW WELLS MISSING COVERS

Window Well(s) lack covers and may represent a danger to small children and may trap pests. A qualified contractor should evaluate and repair or replace as necessary.

4.10.2 – Window Wells
Window Wells 3
Window Wells 4
Window Wells 5WINDOW WELL RUSTED

Window well(s) were rusted or corroded in areas. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.1 – Walkways
Walkways 1
CRACKING – MINOR

Minor cracking was visible on the walkway(s) in areas. Monitoring is the minimum recommendation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.2 – Walkways
Walkways 2
Walkways 3CRACKING – MODERATE

There were signs of moderate cracking on the walkway(s) in areas. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.

4.11.3 – Walkways
Walkways 4
Walkways 5HEAVING AND/OR SETTLING

The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose or it can no longer support the weight causing it to sink or crack.

  • This causes cracks in the concrete.
  • This creates trip hazards that could result in injury.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
Vegetation, Grading & Drainage 2
INADEQUATE CLEARANCE GRADE

The top of the foundation wall had inadequate clearance from grade. The top of the foundation wall should be a minimum of six inches above the soil. Inadequate clearance may result in moisture intrusion of the structure.

Recommend a qualified contractor should evaluate and repair as necessary according to current standards.

4.12.2 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 3
Vegetation, Grading & Drainage 4
NEGATIVE GRADING

The property had areas of neutral or negative drainage, which will route runoff from precipitation to the foundation.  Excessive moisture content in soil supporting the foundation can cause foundation and other structural damage from undermining, heaving, or settling, depending on soil composition, moisture content, and other conditions. The ground around the property should slope away from all sides, ideally 6 inches for the first 10 feet from the house foundation perimeter. Downspouts, surface gutters, and drains should also be directing water away from the foundation. A qualified contractor should evaluate and repair as necessary according to current standards.

4.12.3 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 5
TREE LIMBS CONTACT ROOF

The tree limbs that are in contact with the roof or hanging near the roof should be trimmed. Evaluating trees lies beyond the scope of the general property inspection.

Recommend a qualified contractor to evaluate and repair or replace as necessary.

4.13.1 – Sprinkler System Supply Line
Sprinkler System Supply Line 1
CORRODED – SPRINKLER SUPPLY VALVES

The lawn sprinkler system supply valves appeared to be corroded and/or leaking at the time of inspection. A qualified contractor should evaluate and repair/replace as necessary according to current standards.

4.14.1 – Exterior Faucets (Hose Bibs)
Exterior Faucets (Hose Bibs) 1
DRIPS WHEN OFF

The outside water faucet drips when off. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.18.1 – Exterior Vents
Exterior Vents 1
MISSING VENT COVER

One or more vent cover(s) was missing. A missing vent assembly can allow entry of water, air, or rodents into vent ducts or homes. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.19.1 – Decks & Balconies
Decks & Balconies 1
DAMAGE AT STEP

A step was damaged at the deck. This condition may be a safety hazard.

Correction and further evaluation are recommended.

4.20.1 – Railings & Handrails
Railings & Handrails 1

Railings & Handrails 2

SPINDLE SPACING OVER 4″

Improper spacing was noted between balusters, spindles, and rails. This is a safety hazard, especially for small children.

Guards may not allow the passage of a sphere 4 inches in diameter.

Correction and further evaluation are recommended.

4.21.1 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 1
EXTENSIONS NOT POSITIONED PROPERLY

One or more downspout extensions were not properly positioned. Extensions should be properly attached with a proper slope to guide run-off 5 feet away from the foundation structure.

Recommend a qualified contractor to evaluate and repair or replace as necessary.

4.21.2 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 2
EXTENSIONS DENTED/DAMAGED

Downspout extensions were dented or damaged in some areas at the time of inspection. This condition can cause a blockage and potential build-up of moisture intrusion into the soil next to the foundation walls. This in turn can potentially cause hydro-static pressure against the foundation walls and create adverse results. Recommend further evaluation by a qualified contractor to repair or replace.

4.21.3 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 3
MISSING – EXTENSIONS

The downspout (s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.21.4 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 4
RECONNECT EXTENSION

The downspout (s) need to have extensions reconnected. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in the soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement. When moisture is introduced to the foundation it could also cause possible mold growth. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 5 – Attached Garage
5.2.1 – Occupant Door
NOT FIRE RATED

The inspector was unable to verify that the door was fire rated. This may be considered a fire safety hazard. The door between the garage and the house should be a solid wood door at least 1-3/8 inches thick, a solid or honeycomb-core steel door at least 1-3/8 inches thick, or a 20-minute fire-rated door. This means that should a fire occur in the garage, the occupant door does not afford protection until firemen arrive. A qualified contractor should evaluate and repair or replace as necessary.

5.2.2 – Occupant Door
Occupant Door 1
NOT SELF CLOSING

The door between the garage and the living space failed to close by itself. Modern safety requirements require that the door between the home interior and the garage be self-closing for safety reasons related to fire hazards and toxic fumes. A qualified contractor should evaluate and repair or replace as necessary.

5.3.1 – Ceiling, Walls & Firewalls
Ceiling, Walls & Firewalls 1
FIREWALL BREAK – CEILING

An opening was in the drywall or gypsum board ceiling of the garage.

The ceiling to separate the garage and the living areas, or shared attic space with living areas, should be fire-rated. This ceiling must be covered with at least 1/2-inch thick (and preferably 5/8-inch thick Type X) gypsum board or equivalent applied to the garage side.

Recommend a qualified contractor to evaluate and repair and seal all openings as necessary.

5.6.1 – Door Opener
EXCESSIVE VIBRATION

The garage door and operator motor moved or vibrated excessively when opening/closing. This may relate to a defect with the roller and track assembly, spring assembly, operator motor mount, or possibly the operator motor itself. Recommend a qualified contractor to evaluate and repair or replace as needed.

5.6.2 – Door Opener
Door Opener 1
MISSING – REVERSE SENSORS

The automatic reverse sensors are missing.

These are a safety feature to prevent injury and should be installed no more than 6 inches away from the floor.

5.7.1 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 1
NO GFCI PROTECTION

The garage had one or more outlets without GFCI (or ground fault circuit interrupter) protection.

GFCI protection is required for all 15- and 20-amp receptacles, including outlets for refrigerators, sprinkler systems, garage door openers, and washing machines – some items may not be protected on purpose due to the potential for them to go unnoticed and cause damage. A qualified contractor should evaluate and repair or replace as necessary.

5.7.2 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 2
OUTLET HOT AND NEUTRAL REVERSED

One or more electrical outlet(s) were wired incorrectly with the hot and neutral wires being reversed. While the outlet still provides power to electronic equipment, a shock hazard has been created as there is still electricity running through the hot wire when the switch is off. A qualified contractor should evaluate and repair or replace as necessary according to current standards.

 6 – Interior, Doors, Windows
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
CRACKING AROUND WINDOW

There was cracking around some windows on the interior (where the window meets the wall).  A qualified contractor should evaluate and repair or replace as necessary.

6.2.2 – Ceilings & Walls
Ceilings & Walls 2
MISSING – TRIM

The trim was missing in areas.  A qualified contractor should evaluate and repair or replace as necessary.

6.2.3 – Ceilings & Walls
Ceilings & Walls 3
MINOR CRACKS-WALLS

Minor cracking was visible on the interior walls.  A qualified contractor should evaluate and repair or replace as necessary.

6.4.1 – Doors
Doors 1
GAP AROUND DOOR

The door had an opening that was too wide leaving a gap or daylight around the door.  A qualified contractor should evaluate and repair or replace as necessary.

6.4.2 – Doors
Doors 2
Doors 3
MISSING – DOORSTOP

The door had a damaged or missing doorstop.  A qualified contractor should evaluate and repair or replace as necessary.

6.4.3 – Doors
RUBS FRAME
COUPE BEDROOM CLOSET DOORS

An interior door rubs at the door frame when closing. This may mean the door or frame is out of the square or that hinges may not be installed properly.

A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows
Windows 1
Windows 2
Windows 3
NO EGRESS

At the time of the inspection, the property did not have emergency escape and rescue openings that met generally-accepted current standards. Egress opening requirements:

For safety reasons, all sleeping rooms and basements greater than 200 square feet and new properties should meet the generally-accepted current standards for emergency escape and rescue openings, which include the following requirements:

1. Sill height shall not exceed 44 inches above the floor.

2. Minimum net clear opening shall be 5.7 square feet; exception – grade level windows

may have a minimum clear opening of 5 square feet.

3. Minimum net clear opening height shall be 24 inches.

4. Minimum net clear opening width shall be 20 inches.

6.6.1 – Electrical Outlets
Electrical Outlets 1
Electrical Outlets 2
NOT GROUNDED – OUTLET

One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.

6.10.1 – Installed Heat Source
Installed Heat Source 1
LOW HEAT FURNACE

The supply register supplied lower detectable heat temperatures than adjacent heat sources at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

 7 – Kitchen
7.5.1 – Cabinets & Counters
Cabinets & Counters 1
CAULKING – BACKSPLASH

The countertop needs caulking with silicone along the backsplash.  A qualified contractor should evaluate and repair or replace as necessary.

7.6.1 – Electrical Outlets
GFCI OUTLET NOT GROUNDED

A GFCI outlet was not grounded and did not trip when tested.  A qualified contractor should evaluate and repair or replace as necessary.

 8 – Laundry
8.4.1 – Exhaust Fan
NO VENT NO WINDOW

The laundry room did not have an exhaust fan or an openable window. A qualified contractor should evaluate, then repair or replace as advised.

8.9.1 – Electrical Outlets
Cabinets & Counters 2
GFCI PROTECTION IS NOT PRESENT

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

8.11.1 – Dryer Vent Piping
Dryer Vent Piping 1
DISCONNECTED

A dyer vent connection was installed in the laundry area. The dryer vent connection had become disconnected and should be reconnected to properly route the dryer exhaust to the exterior. Failure to reconnect the vent may result in unsatisfactory conditions from excessive humidity and lint accumulation in the home. Excessively high humidity can damage home materials or components and may encourage the growth of microbes such as mold. A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.7.1 – Electrical Outlets
Electrical Outlets 1
NOT GROUNDED

An electrical outlet was not grounded. A qualified contractor should evaluate and repair or replace as necessary.

9.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
CLOGGED/SLOW – TUB/SHOWER DRAIN

The tub/shower drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.

 11 – Bathroom 3
11.7.1 – Electrical Outlets
Electrical Outlets 1
NOT GROUNDED

An electrical outlet was not grounded. A qualified contractor should evaluate and repair or replace as necessary.

 13 – Electrical
13.8.1 – Service Mast, Service Conduit & Raceway
Service Mast, Service Conduit & Raceway 1
MATERIAL DEFECT

I observed indications of a material defect during the inspection. Major defect. Hazard. Correction and further evaluation are recommended.

13.8.2 – Service Mast, Service Conduit & Raceway
Service Mast, Service Conduit & Raceway 2
ELECTRICAL SERVICE MUST – NOT BE SUPPORTED

The electrical service mast lacked proper support. The mast was over 3 feet tall. Most utility companies will require bracing or guy wires for additional support of any mast that is taller than 3 feet. A qualified electrical contractor should evaluate and repair as necessary.

 14 – Water Heating Equipment
14.3.1 – Pipe Connections
Pipe Connections 1
MISSING FLEX TUBING

The piping to the water heater is missing flex tubing to prevent the piping from breaking in case the concrete floor heaves or settles.

14.6.1 – Combustion Air Supply
NOT PRESENT

The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.

The fresh air supply is recommended by manufacturers for the efficient operation of fuel-burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.

 15 – Heating
15.3.1 – Combustion Air Supply
NOT PRESENT

The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.

The fresh air supply is recommended by manufacturers for the efficient operation of fuel-burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.

15.8.1 – Ductwork
Ductwork 1
DUCTS NOT SEALED

Air supply ducts were not sealed. Ideally, all ducts are sealed with mastic in order to be more energy-efficient. A qualified contractor should evaluate and repair as necessary.

15.9.1 – Air Filter
Air Filter 1
VERY DIRTY

The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.

15.10.1 – Blower
Blower 1
BLOWER WHEEL DIRTY

The blower motor and/or wheel appeared to be dirty at the time of inspection. Blower fan motors and fan wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.

A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.

15.12.1 – Heating System Ignition & Operation
SHORT CYCLING

The furnace was short-cycling (repeated start-up and shut-down within minutes of each other) at the time of the inspection. Most systems should run about 2-3 cycles per hour. A qualified contractor should evaluate and repair or replace as necessary.

 16 – Cooling
16.3.1 – AC Compressor
AC Compressor 1
DENSE VEGETATION

There was dense vegetation around the exterior cooling unit.  When vegetation is too close to the unit, it can limit heat dissipation and limit effectiveness.

A qualified contractor should evaluate and cut back vegetation as necessary to improve performance.

 17 – Structural Crawlspace
17.3.1 – Moisture Intrusion
Moisture Intrusion 1
EFFLORESCENCE

Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, waterproofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.

17.6.1 – Insulation
Insulation1
INSULATION NEEDED

There is no insulation on the crawlspace exterior walls or floor system. Heat loss can occur more on this property than on one that is properly insulated. A qualified contractor should evaluate and install as necessary.

17.6.2 – Insulation
Insulation 2
NOT SECURED LOOSE

The crawl space insulation is not properly secured and is loose in some areas. A qualified contractor should evaluate and repair or replace as necessary.

 18 – Structural Basement
18.3.1 – Foundation Wall
Foundation Wall 1
MINOR CRACKS

There were minor to moderate cracks in the basement foundation wall. These cracks should be sealed to prevent moisture intrusion and monitored for further movement. Further analysis by a licensed structural engineer is recommended. Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540 or online at www.axiuminspections.com/structural-engineer.

18.4.1 – Basement Interior Wall Structure
Basement Interior Wall Structure 1
BASEMENT WALLS NOT FLOATING

Basement walls were not constructed using a method that will allow for soil movement. This method is usually termed “floating” the walls and involves leaving a gap at the bottom of the wall so that vertical movement (heaving) of the concrete slab basement floor will not be transmitted to the rest of the property structure. Colorado has areas with expansive soils. Expansive soils are soils that increase to many times their original volume in response to increases in soil moisture content, creating forces that can easily damage property structural components such as foundations, floor slabs, flat work, and interior and exterior wall coverings. Consider consulting with a qualified contractor before the expiration of your Inspection Objection Deadline to discuss options and costs for correction and/ or stabilization.

18.7.1 – Insulation
Insulation 1
INSULATION NOT SECURED LOOSE

The basement insulation is not properly secured and is loose in some areas. A qualified contractor should evaluate and repair or replace as necessary.

18.8.1 – Vapor Barriers
Vapor Barriers 1
VAPOR BARRIER NOT INSTALLED

A vapor barrier was not installed in the basement at the time of the inspection. A qualified contractor should evaluate and install as necessary.

18.9.1 – Electrical in Basement
Electrical in Basement 1
JUNCTION BOX MISSING COVER PLATE

The splice/Junction box was missing a cover plate. A qualified contractor should evaluate and repair or replace as necessary.