2 – Roof
2.2.1 – Roof Covering
Roof Covering 1
Roof Covering 2
STAINED SHINGLES

The inspector observed stains on the shingles in areas. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.6.1 – Flue Gas Vent Pipes
Flue Gas Vent Pipes 1
CORRODED

One or more combustion exhaust flue(s) showed signs of rust/corrosion.  A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.6.2 – Flue Gas Vent Pipes
Flue Gas Vent Pipes 2
INADEQUATE CLEARANCE – ROOF

One or more combustion appliance exhaust flue(s) did not extend far enough above the roof. To ensure proper and safe operation, exhaust flues should extend at least 3 feet above the roof, and 2 feet above any portion of the roof within 10 feet (measured horizontally).  A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.7.1 – Masonry Chimney
 Masonry Chimney 1
Masonry Chimney 2
DAMAGE – MORTAR CROWN

The mortar crown was damaged, cracked or deteriorated at the time of inspection. This condition could allow moisture to penetrate the chimney. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.7.2 – Masonry Chimney
Masonry Chimney 3
MISSING – RAIN CAP/SPARK ARRESTOR

The chimney rain cap/spark arrestor was missing. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

A rain cap covers the top opening of the chimney flue liner and is usually combined with a spark arrestor.

A spark arrestor is used to prevent floating embers from a solid fuel fire setting light to a flammable roofing surface or falling onto other combustible materials on the ground. A spark arrestor typically consists of a double layer of metal mesh, which catches the ember and allows the flue gas to escape. Spark arrestors also help prevent animals from entering the chimney.

3 – Attic, Insulation and Ventilation
3.4.1 – Insulation in Attic
Insulation in Attic 1
Insulation in Attic 2
TOO THIN

The insulation is thinner than current thermal resistance (R-value) standards.

Recommend a qualified contractor evaluate and repair or replace as needed.

3.5.1 – Ventilation in Attic
Ventilation in Attic 1
VENTILATION INADEQUATE

Ventilation may have been insufficient at the time of the inspection.

Inadequate attic ventilation can cause the attic to overheat, causing heat damage to the roof covering, which results in a decreased life expectancy. Adequate ventilation of the attic will actually help prolong the life expectancy of the roof covering and help stabilize interior temperatures when heating and cooling is in use.

Recommend a qualified contractor evaluate to ensure all attic ventilation is unobstructed and fully functional and/or install additional ventilation as needed.

4 – Exterior
4.2.1 – Driveways
Driveways 1
CRACKING – MODERATE

The concrete driveway was moderately cracked. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.

4.2.2 – Driveways
Driveways 2
DROPPED SURFACE/SLAB

The driveway has dropped or settled in areas, causing a steep or uneven step. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.2.3 – Driveways
Driveways 3
HEAVING AND/OR SETTLING

The driveway showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose, or it can no longer support the weight causing it to sink or crack. This condition could potentially cause a trip hazard.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.2.4 – Driveways
Driveways 4
IMPROPERLY SLOPED SURFACE

The driveway has a negative slope and drains towards the home or garage. This condition is prone to water penetration into the home structure. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.2.5 – Driveways
Driveways 5
PITTED

The driveway surface was pitted in areas. A qualified contractor should evaluate and repair or replace as necessary.

4.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
DAMAGED – SIDING
FRONT GABLE

The siding and/or trim was damaged in areas of the exterior.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.4.2 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 2
Wall-Covering, Flashing & Trim 3
PEELING PAINT
TRIM

Peeling paint was present in areas.

Recommend a qualified contractor should evaluate and repair or replace as needed.

4.4.3 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 4
Wall-Covering, Flashing & Trim 5
Wall-Covering, Flashing & Trim 6
SEAL GAPS AT INTERSECTIONS
MULTIPLE AREAS

Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.

4.4.4 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 7
TUCK POINTING NEEDED

A common maintenance task for brick masonry is the repair of mortar joints. The longevity of mortar joints will vary with the exposure conditions and the mortar materials used, but a life span of more than 25 years is typical. The longevity of brick, however, may well exceed 100 years. Consequently, occasional repair of the mortar joints is expected over the life of the brick masonry. It is our observation that the most common reason for repointing brick masonry is to improve water penetration resistance. Repointing deteriorated mortar joints is one of the most effective and permanent ways of decreasing water entry into brickwork. This is because the most common means of water entry into a brick masonry wall is through de-bonded, cracked or deteriorated mortar joints. A qualified contractor should evaluate and repair all areas as necessary.

4.5.1 – Eaves, Soffits & Fascia
Eaves, Soffits & Fascia 1
GAPS AT INTERSECTIONS

The eaves had gaps at the edges between soffit panels or roof sheathing which allows insects to enter the attic.

Recommend a qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.5.2 – Eaves, Soffits & Fascia
Eaves, Soffits & Fascia 2
WASP NEST

It Wasp nest is present at the time of inspection. Recommend removing by qualified contractor.

4.7.1 – Electrical Fixtures
Electrical Fixtures 1
NOT WORKING – BULB
BACK

A bulb at an exterior light fixture did not respond to the switch at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary according to current standards.

4.11.1 – Walkways
Walkways 1
Walkways 2
IMPROPERLY SLOPED SURFACE
MULTIPLE AREAS

The walkway(s) have a negative slope and drains towards the home in areas. This condition is prone to water penetration into the home structure. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.2 – Walkways
Walkways 3
PITTED

The walkway(s) surface was pitted in areas. A qualified contractor should evaluate and repair or replace as necessary.

4.11.3 – Walkways
Walkways 4
STEPS TOO TALL (OVER 7 3/4″)

One or more steps was too high, and poses a trip hazard. The riser height maximum is 7 3/4 inches measured vertically between the stair treads. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
NEGATIVE GRADING
MULTIPLE AREAS, BACK RIGHT CORNER

The property had areas of neutral or negative drainage, which will route runoff from precipitation to the foundation.  Excessive moisture content in soil supporting the foundation can cause foundation and other structural damage from undermining, heaving or settling, depending on soil composition, moisture content and other conditions.The ground around the property should slope away from all sides, ideally 6 inches for the first 10 feet from the house foundation perimeter. Downspouts, surface gutters and drains should also be directing water away from the foundation. A qualified contractor should evaluate and repair as necessary according to current standards.

4.12.2 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 2
Vegetation, Grading & Drainage 3
TREE BRANCHES OVER PROPERTY

Large trees near the house have branches which overhang the property. Falling branches due to conditions such as wood decay, high winds or heavy snow loads may cause injury, death or damage. Significant weakening of large branches by conditions such as core decay may not be visible by persons without special training. Consider having these trees evaluated by a qualified arborist. Evaluating trees lies beyond the scope of the general property inspection.

Recommend a qualified contractor evaluate and repair or replace as necessary.

4.17.1 – Exterior Foundation Wall
Exterior Foundation Wall 1
Exterior Foundation Wall 2
CRACKS – AT CORNER(S)
MULTIPLE

The exterior foundation wall had cracks at the corner. A qualified contractor should evaluate and repair or replace as necessary.  Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540.

4.17.2 – Exterior Foundation Wall
Exterior Foundation Wall 3
CRACK – SHRINKAGE

The exterior foundation wall had shrinkage crack(s.) A qualified contractor should evaluate and repair or replace as necessary.

4.19.1 – Decks & Balconies
Decks & Balconies 1
CONTACT WITH GROUND

A wood support post or wood portion of the deck was in direct contact with the ground/dirt. The wood should be pressure treated and ideally be: placed in a metal bracket and/or cement casing, and have clearance from the ground level. Wood in direct contact with dirt will wick up ground moisture and deteriorate at an accelerated rate if routine maintenance is not kept.

Recommend a qualified contractor evaluate and repair or replace as needed.

4.19.2 – Decks & Balconies
Decks & Balconies 2
IMPROPERLY SUPPORTED – STRUCTURE

Deck structure was improperly supported. This may be that support posts were connected to the structure (girder, beams) laterally using lag bolts, or beams are incorrectly notched to posts. The beam(s) should be installed on top of or notched partially on top of the support posts. This is a structural defect that may result in injury if not corrected.

A qualified contractor should evaluate and repair or replace as necessary.

4.19.3 – Decks & Balconies
Decks & Balconies 3
IMPROPER FOOTING – SUPPORT POST

A support post was not properly rested on a concrete footer or missing metal connection hardware. This may put the wood in direct contact with the moisture on the ground and accelerate any potential deterioration.

A qualified contractor should evaluate and repair or replace as necessary.

4.19.4 – Decks & Balconies
Decks & Balconies 4
MISSING – LEDGER FLASHING

Flashing was missing at the ledger board. This flashing problem may allow water to enter into the wall cavity or building components. A qualified contractor should evaluate and repair or replace as necessary.

4.20.1 – Railings & Handrails
Railings & Handrails 1
Railings & Handrails 2
LOOSE – HANDRAIL

The guard/hand rail was loose and should be secured. A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

4.20.2 – Railings & Handrails
Railings & Handrails 3
NOT GRASPABLE

A handrail was not graspable.  Graspable is considered 2 inches across the upward face of the rail.

Correction and further evaluation is recommended.

4.20.3 – Railings & Handrails
Railings & Handrails 4

SPINDLE SPACING OVER 4″

Improper spacing was noted between balusters, spindles and rails. This is a safety hazard, especially for small children.

Guards may not allow the passage of a sphere 4 inches in diameter.

Correction and further evaluation is recommended.

4.20.4 – Railings & Handrails
Railings & Handrails 5
Railings & Handrails 6
STAIR-RAILING GAP OVER 6″

Improper gap between stairs and railing.  This is a safety hazard, especially for small children.

An opening, on the open side of a stairs, and bottom rail of the guard should not allow the passage of a sphere 6 inches in diameter.

Correction and further evaluation is recommended.

4.21.1 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 1
Roof Drainage - Downspouts & Extensions 2
EXTENSIONS TOO SHORT

One or more down spout extensions were too short. Recommend installing 6-8ft long (or greater as needed) extensions to divert rainwater runoff away from the property.

4.21.2 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 3
MISSING – EXTENSIONS

Downspout(s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

5 – Attached Garage
5.2.1 – Occupant Door
Occupant Door 1
NOT FIRE RATED

The inspector was unable to verify that the door was fire rated . This may be considered a fire safety hazard. The door between the garage and the house should be a solid wood door at least 1-3/8 inches thick, a solid or honeycomb-core steel door at least 1-3/8 inches thick, or a 20-minute fire-rated door. This means that should a fire occur in garage, the occupant door does not afford protection until firemen arrive. A qualified contractor should evaluate and repair or replace as necessary.

5.2.2 – Occupant Door
Occupant Door 2
NOT SELF CLOSING

The door between the garage and the living space failed to close by itself. Modern safety requirements require that the door between the home interior and the garage be self-closing for safety reasons related to fire hazard and toxic fumes. A qualified contractor should evaluate and repair or replace as necessary.

5.4.1 – Floor
Floor 1
Floor 2
IMPROPERLY SLOPED

The floor surface of the garage is not sloped properly away from the structure due to settlement.

The area of floor used for parking of automobiles or other vehicles must be sloped. It should slope toward the vehicle door opening. The sloped surface will help the movement of liquids to a drain or toward the main vehicle doorway of the carport.

5.6.1 – Door Opener
Door Opener 1
EXTENSION CORD USED

An extension cord was being used to power the garage door operator. Extension cords are for temporary use only, and the operator should be plugged into a dedicated outlet. Recommend a qualified contractor evaluate and update to current building standards as necessary.

5.7.1 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 1
NO GFCI PROTECTION

The garage had one or more outlets without GFCI (or ground fault circuit interrupter) protection.

GFCI protection is required for all 15- and 20-amp receptacles, including outlets for refrigerators, sprinkler systems, garage door openers, and washing machines – some items may not be protected on purpose due to the potential for them to go unnoticed and cause damage. A qualified contractor should evaluate and repair or replace as necessary.

6 – Interior, Doors, Windows
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
ASBESTOS CEILING

The property had ceiling materials that may contain asbestos. Ceiling tiles or popcorn texture were manufactured or installed using asbestos as late as the early 90s.

In the past, asbestos fibers were added during the production to strengthen and increase durability. Materials that contain asbestos, when intact and in good condition, is generally considered non-friable and is not hazardous. Heat, water, weathering or aging can weaken asbestos materials to the point where it is considered friable. Friable material includes any material containing more than 1 percent asbestos that can be crumbled, pulverized or reduced to powder with hand pressure. This includes previously non-friable material which has been damaged to the extent that it may be crumbled, pulverized or reduced to powder by hand pressure and can also be made friable during its removal. Friable materials can release asbestos fibers into the air. Once in the air, asbestos fibers present a health hazard to people who inhale those fibers.

6.2.2 – Ceilings & Walls
Ceilings & Walls 2
Ceilings & Walls 3
Ceilings & Walls 4
DAMAGED – MULTIPLE ITEMS
MULTIPLE AREAS THROUGHOUT PROPERTY

The ceiling and/or walls showed various signs of minor defects at numerous locations including all or some of the following: damage, cracks, holes, previous repairs, and/or improper repairs. A representative number of pictures were taken to provide an example. Should any of these issues appear excessive we recommend a qualified contractor should evaluate and repair or replace items as necessary.

6.3.1 – Floors
Floors 1
CARPET DAMAGED

The carpet was damaged in areas. A qualified contractor should evaluate and repair or replace as necessary.

6.3.2 – Floors
Floors 2
Floors 3
Floors 4
WEAR AND TEAR

The floors showed signs of minor damage and wear, particularly in high-traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows
Windows 1
LOCK NOT WORKING
LIVING ROOM

The window did not lock properly.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.2 – Windows
Windows 2
Windows 3
Windows 4
NO EGRESS

At the time of the inspection, the property did not have emergency escape and rescue openings which met generally-accepted current standards. Egress opening requirements:

For safety reasons, all sleeping room and basements greater than 200 square feet and new properties should meet the generally-accepted current standards for emergency escape and rescue openings, which include the following requirements:

1. Sill height shall not exceed 44 inches above the floor.

2. Minimum net clear opening shall be 5.7 square feet; exception – grade level windows

may have a minimum clear opening of 5 square feet.

3. Minimum net clear opening height shall be 24 inches.

4. Minimum net clear opening width shall be 20 inches.

6.6.1 – Electrical Outlets
Electrical Outlets 1
Electrical Outlets 2
Electrical Outlets 3
NOT GROUNDED – OUTLET
MULTIPLE AREAS

One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.

6.8.1 – Stairways & Railings
Stairways & Railings 1
HIGH STEP

At the interior steps, the risers were taller than acceptable standards.  The risers exceeded 7 3/4″ in height.  A fall or injury could occur if not corrected.  A qualified contractor should evaluate and repair or replace as necessary.

6.8.2 – Stairways & Railings
Stairways & Railings 2
Stairways & Railings 3
NO RETURN AT ENDS

At the interior stairs, the handrail had a railing end that did not return to the wall or post.  A fall could occur if something (purse, backpack etc.) caught the end of the railing when descending. A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

6.8.3 – Stairways & Railings
Stairways & Railings 4
SPINDLE SPACING OVER 4″

At the interior stairs, the handrail had spacing between components that were too far apart. Spacing of more than 4 ” could allow a child or pet to fall through. A fall or injury could occur if not corrected.  A qualified contractor should evaluate and repair or replace as necessary.

6.9.1 – Smoke & CO Detectors
Smoke & CO Detectors 1
Smoke & CO Detectors 2
SMOKE DETECTOR OLD
MULTIPLE

Some of the smoke detectors appeared to be old and beyond their expected life. A qualified person should repair or replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.

7 – Kitchen
7.6.1 – Electrical Outlets
Electrical Outlets 1
OUTLET NOT GROUNDED

An electrical outlet was not grounded. A qualified contractor should evaluate and repair or replace as necessary.

7.13.1 – Dishwasher
Dishwasher 1
NO HIGH LOOP

The dishwasher drain line came out from a low location and did not discharge into a higher drain pipe. Dishwasher drain lines require a “high loop” in the line in order to drain properly. A “high loop” may have been hidden behind the appliance itself. The high loop in the drain hose is to keep water from settling in the hose to prevent any odors from backing up into the dishwasher. Food or debris may become stuck in the line and smell or mold if not corrected. Recommend a qualified contractor evaluate and repair or replace as needed.

7.15.1 – Range Hood
Range Hood 1
LOOSE

The vent hood was loose and not properly secured.  A qualified contractor should evaluate and repair or replace as necessary.

8 – Laundry
8.4.1 – Exhaust Fan
Exhaust Fan 1
NO VENT NO WINDOW

The laundry room did not have an exhaust fan or an openable window. A qualified contractor should evaluate, then repair or replace as advised.

8.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION NOT PRESENT

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

10 – Bathroom 2
10.13.1 – Toilets
Toilets 1
LOOSE AT THE FLOOR

The toilet was loose at the floor. This condition typically is caused by loose bolts or nuts and/or missing floor seals. Loose toilet can result in leaks, water damage, and mold, as well as damage to the toilet, water supply lines, bolts, and drainage pipes. A qualified contractor should evaluate and repair or replace as necessary.

10.14.1 – Tub, Shower Area
Tub, Shower Area 1
DETERIORATED – CAULKING/GROUT

Caulking in the shower/tub area was deteriorated at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.

12 – Electrical
12.2.1 – Distribution Panels
Distribution Panels 1
Distribution Panels 2
ZINSCO PANEL

The main electrical distribution panel was manufactured by Zinsco. These panels have a reputation for being problematic and further evaluation by a qualified electrician is recommended. Zinsco panels can generally be identified by a blue and silver “Zinsco” label inside the panel, an embossed “Magnetrip” label at the top of the panel face, and the colorful breakers.

  • There may be components of the panel that contain aluminum.
  • The connection between the breakers and the bus bar may be defective.
  • The bus bar may be corroded.
  • Breakers may be turned off, but the circuit could still be live.

The obsolete and unreliable Zinsco panel should be further evaluated and replaced by a licensed electrician as necessary.

13 – Water Heating Equipment
13.13.1 – Water Temperature
Water Temperature 1
Water Temperature 2
WATER TEMPERATURE LOW

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

14 – Heating
14.1.1 – Heating System Information
SERVICING RECOMMENDED
Based on the age of the heating system it is recommended that it be cleaned and serviced and certified (if possible) by an HVAC professional.
14.1.2 – Heating System Information
Heating System Information 1
BEYOND TYPICAL LIFE EXPECTANCY

Due to the year (1999) of manufacture, the heating system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.

14.6.1 – Cabinet
Cabinet 1
CORRODED, RUSTED

The heating system cabinet was corroded, rusted or damaged in some areas. A qualified contractor should evaluate and repair or replace as necessary.

14.8.1 – Ductwork
Ductwork 1
DIRTY

The HVAC supply and return ducts were dirty at the time of the inspection and in need of cleaning. Recommend having all the HVAC supply and return ducts cleaned by a qualified contractor.

14.10.1 – Blower
Blower 1
BLOWER WHEEL DIRTY

The blower motor and/or wheel appeared to be dirty at the time of inspection. Blower fan motors and fan wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.

A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.

16 – Cooling – Evaporative Cooler
16.1.1 – System Information
BEYOND TYPICAL LIFE EXPECTANCY

Due to the year of manufacture, the cooling system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.

16.3.1 – Evaporative Pads, Filters
Evaporative Pads, Filters 1
EVAPORATIVE PADS – NEED REPLACEMENT

Recommend replacing the evaporative cooling pads on the swamp cooler and cleaning the reservoir.

16.5.1 – Cooling System Operation
Cooling System Operation 1
DID NOT PRODUCE COOLED AIR

The cooling system turned on but did not operate as expected by producing adequate conditioned cooled air. An ambient air test was performed to determine if the temperatures of the supply air was at least 5 degrees cooler than ambient air. Typical performance of these units is about 5 – 15 degrees of difference. A qualified contractor should evaluate and repair/replace as necessary.

18 – Structural Basement
18.2.1 – Basement Floor
Basement Floor 1
CRACKED – COMMON

The concrete floor in the basement was cracked in areas. These cracks appear to be common cracks indicating regular settlement or heaving, but not necessarily structural problems. Recommend a qualified contractor to evaluate to make further recommendations and repair as necessary.

Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540.

18.5.1 – Moisture Intrusion
Moisture Intrusion 1
EFFLORESCENCE

Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, a water proofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.