4 – Exterior
4.4.1 – Wall-Covering, Flashing & Trim

Wall-Covering, Flashing & Trim 1

Wall-Covering, Flashing & Trim 2

CRACKING – MINOR
Siding showed cracking and or damage in one or more places. Recommend monitoring, and if the problem exacerbates, a qualified contractor should evaluate and repair or replace as necessary and according to current standards.
4.4.2 – Wall-Covering, Flashing & Trim

Wall-Covering, Flashing & Trim 3

SEAL GAPS AT INTERSECTIONS
MULTIPLE AREAS

Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.

4.4.3 – Wall-Covering, Flashing & Trim

Wall-Covering, Flashing & Trim 4

SIGNS OF REPAIRS

There were signs of previously repaired damage. Recommend inquiring with current homeowners for any further information. Should repairs be significant or failing, we recommend a qualified contractor should evaluate and repair or replace as needed.

4.5.1 – Eaves, Soffits & Fascia

Eaves, Soffits & Fascia 1

GAPS AT INTERSECTIONS

The eaves had gaps at the edges between soffit panels or roof sheathing which allows insects to enter the attic.

Recommend a qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.6.1 – Exterior Doors
Exterior Doors 1
DAMAGED – DOORBELL BUTTON

The doorbell button was missing or damaged at the time of the inspection. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.10.1 – Window Wells
Window Wells 1
WINDOW WELLS MISSING COVERS

Window Well(s) lacked covers and may represent a danger to small children and may trap pests. A qualified contractor should evaluate and repair or replace as necessary.

4.10.2 – Window Wells

Window Wells 2

WINDOW WELL DAMAGED

Window Well(s) were damaged. A qualified contractor should evaluate and repair or replace as necessary according to current standards.

4.11.1 – Walkways

Walkways 1

CRACKING – MINOR

Minor cracking was visible on the walkway(s) in areas. Monitoring is the minimum recommendation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.2 – Walkways
Walkways 2

Walkways 3

HEAVING AND/OR SETTLING

The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose or it can no longer support the weight causing it to sink or crack.

  • This causes cracks in the concrete.
  • This creates trip hazards that could result in injury.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
DENSE VEGETATION

Dense vegetation was present around the house in areas.  This condition limited and restricted my visual inspection.  Dense vegetation and landscaping up against or near the house foundation and exterior walls may be prone to water penetration and insect infestation. Trimming, pruning and some landscaping is recommended by a qualified contractor

4.14.1 – Exterior Faucets (Hose Bibs)
DRIPS AT KNOB
FRONT

The outside water faucet drips at the knob when turned on. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.21.1 – Roof Drainage – Downspouts & Extensions

Roof Drainage - Downspouts & Extensions 1

RECONNECT TO DRAIN

Downspout(s) need reconnecting to existing drain line. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement. When moisture is introduced to the foundation it could also cause possible mold growth. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

5 – Attached Garage
5.6.1 – Door Opener
Door Opener 1
REVERSE SENSORS TOO HIGH

The photo-electric reverse sensors are installed too high from the garage floor surface.

The vertical distance between the photo-eye beam and the floor should be no more than 6 inches.

6 – Interior, Doors, Windows
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
Ceilings & Walls 2
DAMAGED – TRIM
MINOR DAMAGE THROUGHOUT THE PROPERTY

Accent trim was damaged at areas of the interior walls at the time of inspection.

Recommend a qualified contractor evaluate and repair or replace as needed.

6.2.2 – Ceilings & Walls
Ceilings & Walls 3
Ceilings & Walls 4
DAMAGED – WALLS

The walls showed signs of minor damage and wear.  A qualified contractor should evaluate and repair or replace as necessary.

6.2.3 – Ceilings & Walls
Ceilings & Walls 5
DAMAGED – WALLS
HOLE IN THE WALL GUEST BEDROOM

The walls showed signs of minor damage and wear.  A qualified contractor should evaluate and repair or replace as necessary.

6.3.1 – Floors
Floors 1
CARPET DAMAGED
MULTIPLE AREAS THROUGHOUT PROPERTY

The carpet was damaged in areas. A qualified contractor should evaluate and repair or replace as necessary.

6.3.2 – Floors

Floors 2

MISSING TRANSITION PIECE

A transition piece was missing between two sections of flooring.  A qualified contractor should evaluate and repair or replace as necessary.

6.3.3 – Floors
Floors 3
WEAR AND TEAR
THROUGHOUT PROPERTY

The floors showed signs of minor damage and wear, particularly in high-traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows
Floors 1
SCREENS DAMAGED/MISSING
ONE OR MORE

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

6.7.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
NOT WORKING – BULB(S)
FIRST FLOOR GUEST BEDROOM

One or more light bulbs were not working at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as needed.

6.7.2 – Electrical Fixtures & Switches

Electrical Fixtures & Switches 2

FAN NOT WORKING
FIRST FLOOR GUEST BEDROOM

The ceiling fan did not work. A qualified contractor should evaluate and repair or replace as necessary.

7 – Kitchen 
7.4.1 – Floors
Floors 1
WEAR AND TEAR

The floors showed signs of minor damage and wear – particularly in high traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

7.5.1 – Cabinets & Counters
Cabinets & Counters 1
CAULKING – BACKSPLASH

The counter top needs caulking with silicone along the back splash.  A qualified contractor should evaluate and repair or replace as necessary.

7.5.2 – Cabinets & Counters
Cabinets & Counters 2
WORN FINISH

Counters or cabinetry had a finish that was worn or peeling. Recommend a qualified contractor evaluate and repair or replace as needed.

7.12.1 – Food Waste Disposer
Food Waste Disposer 1
Food Waste Disposer 2
NOT WORKING
RESET BUTTON DID NOT WORK

The food waste disposer was not working at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

8 – Laundry
8.4.1 – Exhaust Fan
Exhaust Fan 1
LOOSE
LAUNDRY AREA

The laundry area exhaust fan was loose.  A qualified contractor should evaluate and repair or replace as necessary.

8.4.2 – Exhaust Fan
Exhaust Fan 2
DIRTY
LAUNDRY AREA

The laundry area exhaust fan was dirty. The fan could eventually become clogged or damaged if not cleaned.  A qualified contractor should evaluate and repair or replace as necessary.

8.5.1 – Ceilings & Walls

Ceilings & Walls 1

MOISTURE DAMAGE-WALLS
LAUNDRY AREA

The interior walls showed evidence that moisture was entering from behind possibly including damage and deterioration.  A qualified contractor should evaluate and repair or replace as necessary.

8.9.1 – Floors
Floors 1
WEAR AND TEAR
The floors showed signs of minor damage and wear – particularly in high traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.
9 – Bathroom 
9.5.1 – Floors
Floors 2
WEAR AND TEAR

The floors showed signs of minor damage and wear – particularly in high traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

9.9.1 – Cabinets & Counters
Cabinets & Counters 1
LOOSE – CABINETRY

The base cabinetry was loose and not securely fastened to the wall.  A qualified contractor should evaluate and repair or replace as necessary.

10 – Bathroom 2
10.5.1 – Floors

Floors 1

MISSING TRANSITION PIECE
A transition piece was missing between two sections of flooring.  A qualified contractor should evaluate and repair or replace as necessary.
10.8.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
NOT WORKING – BULB

One or more bulbs was not working in the bathroom at the time of inspection.

Recommend a qualified contractor evaluate and repair or replace as needed.

10.9.1 – Cabinets & Counters
Cabinets & Counters 1
CAULKING – BACK SPLASH

The counter top needs caulking with silicone along the back splash.  A qualified contractor should evaluate and repair or replace as necessary.

10.9.2 – Cabinets & Counters
Cabinets & Counters 2
WORN FINISH

Wood cabinetry had a finish that was worn or peeling. Recommend a qualified contractor evaluate and repair or replace as needed.

10.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
MISSING – SINK DRAIN STOPPER
EN SUITE GUEST BATHROOM 1ST FLOOR

The sink drain stop was missing, damaged or did not operate properly.  A qualified contractor should evaluate and repair or replace as necessary.

10.14.1 – Tub, Shower Area
Tub, Shower Area 1
CAULK – CORNERS AND FLOOR

The tub/shower area had deteriorated or missing sealant (caulking or grout) at the corners and/or floor. Sealant is needed at wall corners inside the shower, corners from tub to wall, and along the floor perimeter.  A qualified contractor should evaluate and repair or replace as necessary.

10.15.1 – Fixture Valve Installation And Temperature
Fixture Valve Installation And Temperature 1
WATER NOT HOT
1ST FLOOR BATHROOM

The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.

Hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.

Recommend a qualified contractor evaluate and repair or replace as necessary.

11 – Bathroom 3
11.5.1 – Floors

Floors 1

MISSING TRANSITION PIECE

A transition piece was missing between two sections of flooring.  A qualified contractor should evaluate and repair or replace as necessary.

11.5.2 – Floors
Floors 2
WEAR AND TEAR

The floors showed signs of minor damage and wear – particularly in high traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

11.15.1 – Fixture Valve Installation And Temperature
Fixture Valve Installation And Temperature 1
WATER NOT HOT

The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.

Hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.

Recommend a qualified contractor evaluate and repair or replace as necessary.

12 – Electrical
12.2.1 – Distribution Panels
Distribution Panels 1
MISSING – CIRCUIT LABELS

The circuit labels were missing, partial, or illegible at the electrical distribution panel. The circuit labels provide information describing the locations each individual circuit breaker provides power too.

Recommend a qualified contractor verify the breakers and accuracy of any existing labeling as necessary.

13 – Plumbing
13.4.1 – Water Pressure
Water Pressure 1
LOW WATER PRESSURE
SLIGHTLY LOW WATER PRESSURE

The property water supply pressure was measured at the exterior faucet or laundry hose bib. Property water supply pressure was lower than the 40 pounds per square inch (PSI), which is considered inadequate by generally-accepted current standards.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

14 – Water Heating Equipment
14.10.1 – Drain Valve & Drip Pan
Drain Valve & Drip Pan 1
MISSING DRAIN LINE

The drip pan for the water heating equipment did not have a drain line attached. A qualified contractor should evaluate and repair or replace as necessary.

14.13.1 – Water Temperature
Water Temperature 1
Water Temperature 2
WATER TEMPERATURE LOW

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

15 – Cooling
15.1.1 – Cooling System Information
SERVICING RECOMMENDED
Based on the age of the cooling system it is recommended that it be cleaned and serviced and certified (if possible) by an HVAC professional.
15.2.1 – AC Refrigerant Lines
AC Refrigerant Lines 1
GAP AROUND LINE AT WALL

The air-conditioner refrigerant suction line (large, insulated) exterior wall penetration should be sealed to prevent moisture and insect intrusion. A qualified contractor should evaluate and repair/replace as necessary.

15.3.1 – AC Compressor
AC Compressor 1
UNIT IS NOT LEVEL

The exterior compressor unit was not level. Over time, this may result in noisy fan operation, damage to the fan bearings and a shortened fan lifespan, or it may result in movement of the compressor housing which can cause leaks in refrigerant lines resulting in expensive service. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

15.7.1 – Evaporator Coils
Evaporator Coils 1
GAP AT REFRIGERANT LINES

There was a gap where the refrigerant lines enter the plenum. Recommend a qualified contractor evaluate and seal as needed.

16 – Heating
16.9.1 – Air Filter
Air Filter 1
FILTER WRONG SIZE

The HVAC system air filter was incorrectly sized. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict air flow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing filter, as well as cleaning, servicing and evaluating of the HVAC system by a qualified HVAC professional and repair or replace as necessary.