The built up roofing on the low slope roof above the addition had displaced gravel and wear and appearedĀ to be older than the rest of the roof. A qualified contractor should evaluate and repair overplace as necessary.
The chimney rain cap/spark arrestor was missing. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.
A rain cap covers the top opening of the chimney flue liner and is usually combined with a spark arrestor.
A spark arrestor is used to prevent floating embers from a solid fuel fire setting light to a flammable roofing surface or falling onto other combustible materials on the ground. A spark arrestor typically consists of a double layer of metal mesh, which catches the ember and allows the flue gas to escape. Spark arrestors also help prevent animals from entering the chimney.
The chimney had deteriorated mortar joints at the time of inspection and may require repairs such as “tuck-pointing” or “re-pointing”. This is a common maintenance task for masonry. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.
Signs of previous water penetration or intrusion into the attic. Water marks or stains were observed. Recommend asking seller if there’s any recent incidents that have been documented or mitigated.
Further evaluation is recommended.
The insulation is not uniform: thicker in areas, thinner in areas, or possibly missing in some areas.
Recommend a qualified contractor evaluate and repair or replace as needed.
Recommend a qualified contractor evaluate and repair or replace as needed.
The exterior wall covering is beginning to deteriorate or has deteriorated.
Recommend a qualified contractor should evaluate and repair or replace as needed.
The distance between the bottom of wood components and the ground surface (or grade) was not sufficient. There should be a 6 inch gap between the bottom of siding and ground and a 2 inch gap between the bottom of siding and hard surfaces.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
A common maintenance task for brick masonry is the repair of mortar joints. The longevity of mortar joints will vary with the exposure conditions and the mortar materials used, but a life span of more than 25 years is typical. The longevity of brick, however, may well exceed 100 years. Consequently, occasional repair of the mortar joints is expected over the life of the brick masonry. It is our observation that the most common reason for repointing brick masonry is to improve water penetration resistance. Repointing deteriorated mortar joints is one of the most effective and permanent ways of decreasing water entry into brickwork. This is because the most common means of water entry into a brick masonry wall is through de-bonded, cracked or deteriorated mortar joints. A qualified contractor should evaluate and repair all areas as necessary.
A GFCI outlet was not grounded and did not trip when tested. A GFCI requires a ground wire to route electricity when tripped. Although GFCI protection of exterior circuits may not have been required at the time in which this property was built, modern building and safety standards now require them. This is a reflection of the current understanding of the potential hazards. The inspector recommends updating the existing exterior electrical circuits to include GFCI protection. A qualified contractor should evaluate and implement according to current standards.
The property had basement windows at grade level without window wells installed. This could allow water intrusion into property at this point. A qualified contractor should evaluate and repair/replace as necessary.
There were signs of moderate cracking on the walkway(s) in areas. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.
There were signs of significant cracking on the walkway(s) in areas. Cracks that with a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. These cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.
The walkway(s) showed signs of heaving and/or settling in areas. Heaving is often caused by soil that has expanded in volume due to increased moisture content, or by wet soil which has expanded as it became frozen. Settlement is when the soil below a concrete slab is loose or it can no longer support the weight causing it to sink or crack.
- This causes cracks in the concrete.
- This creates trip hazards that could result in injury.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
A trip hazard was present on the walkway(s) in areas. Ā This condition is a safety concern. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
The property had areas of neutral or negative drainage, which will route runoff from precipitation to the foundation. Ā Excessive moisture content in soil supporting the foundation can cause foundation and other structural damage from undermining, heaving or settling, depending on soil composition, moisture content and other conditions.The ground around the property should slope away from all sides, ideally 6 inches for the first 10 feet from the house foundation perimeter. Downspouts, surface gutters and drains should also be directing water away from the foundation. A qualified contractor should evaluate and repair as necessary according to current standards.
The tree limbs that are in contact with the roof or hanging near the roof should be trimmed. Evaluating trees lies beyond the scope of the general property inspection.
Recommend a qualified contractor evaluate and repair or replace as necessary.
The outside water faucet drips at the knob when turned on. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
One or more vent cover(s)Ā was missing. A missing vent assembly can allow entry of water, air, or rodents into vent ducts or home. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
A railing height was measured less than 36 inches. This is a safety hazard for small children.
Guardrails are normally required to be 36 inches above standing surface next to the guardrail.
Correction and further evaluation is recommended.
Downspout(s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
Minor cracking was visible on the interior ceilings. Ā A qualified contractor should evaluate and repair or replace as necessary.
Minor cracking was visible on the interior walls. Ā A qualified contractor should evaluate and repair or replace as necessary.
The tile floor was cracked/damaged. Ā A qualified contractor should evaluate and repair or replace as necessary.
The floors showed signs of minor damage and wear, particularly in high-traffic areas. Ā A qualified contractor should evaluate and repair or replace as necessary.
The closet door was very difficult to slide on the track. Ā A qualified contractor should evaluate and repair or replace as necessary.
The sliding/folding door would fall off the track when operated. Ā A qualified contractor should evaluate and repair or replace as necessary.
The door swings over the top step of the stairwell when opened. Ā This can lead to a fall and is considered a safety hazard. Ā A qualified contractor should evaluate and repair or replace as necessary.
At the time of the inspection, the property did not have emergency escape and rescue openings which met generally-accepted current standards. Egress opening requirements:
For safety reasons, all sleeping room and basements greater than 200 square feet and new properties should meet the generally-accepted current standards for emergency escape and rescue openings, which include the following requirements:
1. Sill height shall not exceed 44 inches above the floor.
2. Minimum net clear opening shall be 5.7 square feet; exception – grade level windows
may have a minimum clear opening of 5 square feet.
3. Minimum net clear opening height shall be 24 inches.
4. Minimum net clear opening width shall be 20 inches.
Several electrical outlets were not grounded throughout the property. A qualified contractor should evaluate and repair or replace as necessary.
One or more light bulbs wereĀ not working at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as needed.
The ceiling fan was noisy when on. Ā A qualified contractor should evaluate and repair or replace as necessary.
At the interior stairs, the handrail had a railing end that did not return to the wall or post. Ā A fall could occur if something (purse, backpack etc.) caught the end of the railing when descending. A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.
Carbon monoxide detectors were not installed within a specified distance of each room lawfully used for sleeping purposes. The inspector recommends installation of carbon monoxide detectors in appropriate locations. Colorado House bill 1091 became effective on July 1, 2009 that requires Carbon Monoxide detectors to be installed in most properties that has a fuel-burning heater or appliance, a fireplace, or an attached garage.
There are no carbon monoxide detectors on the lower or upper level.
There was no heat source installed. Ā A qualified contractor should evaluate and repair or replace as necessary.
One kitchen drawer had a loose drawer front. A qualified contractor should evaluate and repair or replace as necessary.
The revolving shelf was difficult to move. A qualified contractor should evaluate and repair or replace as necessary.
Some windows had damaged or missing screens. Ā A qualified contractor should evaluate and repair or replace as necessary.
The light fixture did not operate when switch was turned on. Try replacing bulb first. A qualified contractor should evaluate and repair or replace as necessary.
The sink drain line had a flex pipe used as part of the drain line. Flexible drain lines can smell, clog, leak or fail. Flex lines design includes multiple folds in which moisture may become trapped and mold may grow. Ā A qualified contractor should evaluate and repair or replace as necessary.
The food waste disposer was noisy or damaged when operated. It may be that this appliance has an improper item stuck in it and it may be this appliance is worn or aged. A qualified contractor should evaluate and repair or replace as necessary.
The dishwasher rack was missing one or more wheels. Ā A qualified contractor should evaluate and repair or replace as necessary.
The microwave vent hood had a gap between the bottom of the cabinet and the top of the vent hood. This creates a space between the vent and the hood possibly allowing airflow in the gap. A qualified contractor should evaluate and repair or replace as necessary.
The water and ice feature at the refrigerator was not working at the time of the inspection. A qualified contractor should evaluate, then repair or replace as advised.
The floors showed signs of minor damage and wear – particularly in high traffic areas. Ā A qualified contractor should evaluate and repair or replace as necessary.
A GFCI outlet was not grounded and did not trip when tested. A GFCI requires a ground wire to route electricity when tripped. A qualified contractor should evaluate and repair or replace as necessary.
The bathtub drain stop was damaged, missing or did not operate properly. Ā A qualified contractor should evaluate and repair or replace as necessary.
The drain stop did not work or did not hold water in the sink. Ā A qualified contractor should evaluate and repair or replace as necessary.
The diverter valve that diverts water from the tub spout to the shower head was leaking while in the shower position. This may be an indication of the valve beginning to fail.
A qualified contractor should evaluate and repair or replace as necessary.
There was a leak at the shower head connection at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.
The overall ceiling height above the bathtub/shower was too short. The height should be a minimum of 80 inches over a majority of the tub. A qualified contractor should evaluate and repair or replace as necessary.
A GFCI outlet was not grounded and did not trip when tested. A GFCI requires a ground wire to route electricity when tripped. A qualified contractor should evaluate and repair or replace as necessary.
The sink drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.
The drain stop did not work or did not hold water in the sink. Ā A qualified contractor should evaluate and repair or replace as necessary.
The toilet was slow to fill when flushed. Ā A qualified contractor should evaluate and repair or replace as necessary.
The toilet seat was loose or damaged. Ā A qualified contractor should evaluate and repair or replace as necessary.
The tub/shower area had deteriorated or missing sealant (caulking or grout) where the shower wall rests on the tub and/or at the inside corners. A qualified contractor should evaluate and repair or replace as necessary.
The sink drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.
The sink drain pipe was leaking at the time of inspection. Ā A qualified contractor should evaluate and repair or replace as necessary.
There were no water supply valves installed at the sink at the time of inspection. Ā A qualified contractor should evaluate and repair or replace as necessary.
The basement windows were not energy efficient and would allow cold air to pass between the panes. A qualified contractor should evaluate and repair or replace as necessary.
A GFCI outlet was not grounded and did not trip when tested. A GFCI requires a ground wire to route electricity when tripped. A qualified contractor should evaluate and repair or replace as necessary.
The tub/shower area had deteriorated or missing sealant (caulking or grout) at the corners and/or floor. Sealant is needed at wall corners inside the shower, corners from tub to wall, and along the floor perimeter. Ā A qualified contractor should evaluate and repair or replace as necessary.
The water supply valves and supply lines at the sink fixture in the bathroom were installed improperly with a reversed configuration. Current standards for installation produce hot water when the valve is turned to the left and cold water when the valve is turned to the right. A qualified contractor should evaluate and repair or replace as necessary.
The sink was cracked or damaged. Ā A qualified contractor should evaluate and repair or replace as necessary.
The property water supply pressure Ā measured at the exterior faucet or laundry appliance hose bib. Property water supply pressure exceeded the 80 pounds per square inch (PSI) limit considered the maximum allowable by generally accepted current standards. Excessively high water pressure can stress connections in the plumbing system and appliances is likely to cause leaks.
A qualified contractor should install a pressure regulator or evaluate and repair or replace one as necessary.
The manufacturer’s label was missing, partial, or illegible at the Ā electrical service panel. The manufacturer’s label typically provides information describing the main panel such as the name of the panel manufacturer, the panel model number, the panel amperage rating, limitations related to the environment in which the panel was designed to be installed and grounding/bonding information for that particular model. The Inspector was unable to confirm the existence of proper conditions when confirmation would require information taken from this missing label.
Panel cover wonāt stay open without a prop. This is a potential safety hazard for working on the panel.
There were two former electrical panels that are no junction boxes. These covers should be screwed shut since there are live wires inside. A qualified contractor should evaluate and repair or replace as necessary.
The TPRV pipe did not conspicuously terminate within 6 inches of the floor. This may allow high pressure hot water to cause unnecessary damage. A qualified contractor should evaluate and repair or replace as necessary.
The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.
Due to the year of manufacture, the heating system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible.
The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.
Fresh air supply is recommended by manufacturers for efficient operation of fuel burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.
The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.
Replacement of the air filter was very difficult because of the size of the opening. A qualified contractor should evaluate and repair or replace as necessary.
The manufacturing label on the system was worn out and illegible. This is an indication of old age, or prolonged exposure to harsh elements. Recommend a qualified contractor further evaluate and repair or replace.
Although outside the scope of normal home inspection in the inspectors opinion the air conditioning condenser unit appeared to be undersized for this size of house. A qualified contractor should evaluate and repair or replace as necessary.
The exterior compressor unit was not level. Over time, this may result in noisy fan operation, damage to the fan bearings and a shortened fan lifespan, or it may result in movement of the compressor housing which can cause leaks in refrigerant lines resulting in expensive service. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
No soil cover was installed at the time of the inspection. Soil covers help reduce humidity levels in crawlspaces by limiting moisture evaporation into the air from soil. Reducing humidity levels can help reduce the chances for mold growth and deterioration of structural components. A qualified contractor should evaluate and install a soil cover as necessary.
Some of the mortar between the stones of the foundation was missing and deteriorated. A qualified contractor should evaluate and repair or replace as necessary.
Indications of movement/settling of the concrete floor were present in the basement area. This may be a compromise to the structural integrity of the foundation or structure of the house which only a qualified structural engineer could comment after further analysis.
Recommend a qualified structural engineer inspect further and provide a professional opinion related to this observation.
Axium recommends our premier partner – Level Engineering. They can be contacted at 720-706-8540.
Basement walls were not constructed using a method which will allow for soil movement. This method is usually termed “floating” the walls and involves leaving a gap at the bottom of the wall so that vertical movement (heaving) of the concrete slab basement floor will not be transmitted to the rest of the property structure. Colorado has areas with expansive soils. Expansive soils are soils which increase to many times their original volume in response to increases in soil moisture content, creating forces which can easily damage property structural components such as foundations, floor slabs, flat work and interior and exterior wall coverings. Consider consulting with a qualified contractor before the expiration of your Inspection Objection Deadline to discuss options and costs for correction an/ or stabilization.
Efflorescence (white powdery substance) on the wall indicates moisture is in contact with the concrete or masonry. This does not necessarily indicate that intrusion will occur. I recommend checking the gutters and the downspout drain lines for proper operation. Also, a water proofing paint could be applied to the interior side of the wall if necessary. Efflorescence is found on many properties without water intrusion occurring inside the property. But, it should alert you to the possibility that future steps may be needed. A qualified contractor should evaluate and repair as necessary.