2 – Roof
2.2.1 – Roof Covering
Roof Covering 1
DAMAGED/DETERIORATED

The roof covering material was damaged/deteriorated in some areas.  A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.2.2 – Roof Covering
Roof Covering 2
Roof Covering 3
DEGRANULATED

Some of the shingles appeared to be de-granulated in areas. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

 4 – Exterior
4.2.1 – Driveways
Driveways 1
PITTED

The driveway surface was pitted in areas. A qualified contractor should evaluate and repair or replace as necessary.

4.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
CRACKING – MINOR

Siding showed cracking and or damage in one or more places. Recommend monitoring, and if the problem exacerbates, a qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.4.2 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 2
MUD TUBES

Mud tubes are present at the exterior at the time of inspection. Mud tubes are generally formed by wood destroying insects. Recommend a qualified contractor evaluate and repair or replace as needed.

4.18.1 – Exterior Vents
Exterior Vents 1
MISSING SCREEN

One or more vent was missing a screen. A damaged vent assembly can allow entry of water, air, or rodents into vent ducts or home.  Recommend a qualified contractor to evaluate and repair or replace as necessary.

4.20.1 – Railings & Handrails
Railings & Handrails 1
MISSING – HANDRAIL
A stairway of more than 3 steps or drop of over 30″ was missing a handrail.

 5 – Attached Garage

5.4.1 – Floor
Floor 1
PITTED

The garage floor was pitted in areas the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.

 6 – Interior, Doors, Windows
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
DAMAGED – WALLS

The walls showed signs of minor damage and wear.  A qualified contractor should evaluate and repair or replace as necessary.

6.7.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
CAN’T FIND SWITCH

A light fixture was not inspected because the switch could not be located. A qualified contractor should evaluate and repair or replace as necessary.

 7 – Kitchen
7.5.1 – Cabinets & Counters
Cabinets & Counters 1
GROUT – BACKSPLASH

The tile backsplash had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.5.1 – Floors
Floors 1
MISSING TRANSITION PIECE

A transition piece was missing between two sections of flooring.  A qualified contractor should evaluate and repair or replace as necessary.

9.13.1 – Toilets
Toilets 1
LOOSE AT THE FLOOR

The toilet was loose at the floor. This condition typically is caused by loose bolts or nuts and/or missing floor seals. Loose toilet can result in leaks, water damage, and mold, as well as damage to the toilet, water supply lines, bolts, and drainage pipes. A qualified contractor should evaluate and repair or replace as necessary.

 10 – Bathroom 2
10.5.1 – Floors
Floors 1
MISSING TRANSITION PIECE

A transition piece was missing between two sections of flooring.  A qualified contractor should evaluate and repair or replace as necessary.

 11 – Bathroom 3
11.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
NOT WORKING – STOPPER

The sink was missing the stopper or it did not work properly at the time of the inspection. Recommend a qualified contractor evaluate and repair or replace as needed.

11.15.1 – Fixture Valve Installation And Temperature
Fixture Valve Installation And Temperature 1
WATER NOT HOT

The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.

Hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.

Recommend a qualified contractor evaluate and repair or replace as necessary.

 12 – Bathroom 4
12.15.1 – Fixture Valve Installation And Temperature
Fixture Valve Installation And Temperature 2
WATER NOT HOT

The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.

Hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.

Recommend a qualified contractor evaluate and repair or replace as necessary.

 14 – Electrical
14.2.1 – Distribution Panels
Distribution Panels 1
INADEQUATE WORKSPACE – PANEL

The distribution panel had inadequate clear space that is 3 feet deep, 30 inches wide, and 6′ 6″ in height in front of the equipment. A qualified contractor should evaluate and repair or replace as necessary.

14.2.2 – Distribution Panels
Distribution Panels 2
LABELS FADED.
 15 – Water Heating Equipment
15.4.1 – Expansion Tank / Valve
Expansion Tank / Valve 1
NOT SECURED

The expansion tank was not properly secured. A qualified contractor should evaluate and repair or replace as necessary.

 16 – Heating
16.9.1 – Air Filter
Air Filter 1
VERY DIRTY

The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.

16.10.1 – Blower
Blower 1
BLOWER, CABINET DIRTY

The blower motor, wheel, and/or cabinet appeared to be dirty at the time of inspection. Blower fans/wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.

A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.

 17 – Cooling
17.3.1 – AC Compressor
AC Compressor 1
UNIT IS NOT LEVEL

The exterior compressor unit was not level. Over time, this may result in noisy fan operation, damage to the fan bearings and a shortened fan lifespan, or it may result in movement of the compressor housing which can cause leaks in refrigerant lines resulting in expensive service. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.