3 – Attic, Insulation and Ventilation
3.6.1 – Electrical Wiring In Attic
Electrical Wiring In Attic 1
JUNCTION BOX MISSING COVER PLATE
Splice/Junction box was missing a cover plate. A qualified contractor should evaluate and repair or replace as necessary.
3.6.2 – Electrical Wiring In Attic
Electrical Wiring In Attic 2
LIGHT NOT WORKING
A light in the attic was not working at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.
 4 – Exterior
4.2.1 – Driveways
Driveways 1
Driveways 2
CRACKING – MINOR

Minor cracking was visible on the driveway in areas. Monitoring is the minimum recommendation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.2.2 – Driveways
Driveways 3
SPALLING

The driveway surface was spalling in areas. This condition will continue to degrade if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

4.8.1 – Electrical Outlets
Electrical Outlets 1
MISSING – COVER PLATE
BACK

The exterior electrical outlet was missing a cover plate along with a weatherproof covering. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.10.1 – Window Wells
Window Wells 1
WINDOW WELL NO LADDER

Window well(s) lacked an egress ladder. Window wells more that 44″ below grade should have a permanent ladder installed. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.1 – Walkways
Walkways 1
CRACKING – MINOR
BACK

Minor cracking was visible on the walkway(s) in areas. Monitoring is the minimum recommendation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.2 – Walkways
Walkways 2
IMPROPERLY SLOPED SURFACE
BACK

The walkway(s) have a negative slope and drains towards the home in areas. This condition is prone to water penetration into the home structure. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.11.3 – Walkways
Walkways 3
Walkways 4
SIGNS OF REPAIRS
FRONT

Signs of repairs were present in the walkway(s) in areas. Recommend asking current homeowner for more information, and if repairs appear to be of poor quality it is recommended to have a qualified contractor evaluate further for any additional repairs necessary.

4.14.1 – Exterior Faucets (Hose Bibs)
LOOSE IN WALL

One or more exterior faucet was loose in the wall. The faucet should be securely fastened to the wall using appropriate screws depending on the material at the location of the faucet. Recommend a qualified contractor evaluate and repair or replace as needed.

4.15.1 – Sump Pump Discharge Pipe
Sump Pump Discharge Pipe 1
DISCHARGE TOO CLOSE

The sump pump discharge pipe did not terminate far enough away from the foundation. Erosion can continue or become worse if not corrected possibly leading to water intrusion. This condition may cause problems by introducing excessive amounts of moisture to the soil near the foundation. A qualified contractor should evaluate and install a proper extension, to properly route drainage away from the foundation, usually at least 6 feet.

4.21.1 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 1
MISSING – EXTENSIONS
FRONT LEFT

Downspout(s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 5 – Attached Garage
5.6.1 – Door Opener
Door Opener 1
REVERSE SENSORS TOO HIGH

The photo-electric reverse sensors are installed too high from the garage floor surface.

The vertical distance between the photo-eye beam and the floor should be no more than 6 inches.

5.7.1 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 1
NOT WORKING – BULB

Light bulbs flickering to controls in the garage.

Recommend a qualified contractor evaluate and repair or replace as needed.

 6 – Interior, Doors, Windows
6.4.1 – Doors
Doors 1
MISSING – FLOOR GUIDES
FRONT OFFICE ROOM

The door had missing or damaged floor guides.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows
Windows 1
Windows 2
SCREENS DAMAGED/MISSING
BASEMENT

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.2 – Windows
Windows 3
WATER PENETRATION
FRONT OFFICE ROOM

Signs of water penetration was present at the window(s).  A qualified contractor should evaluate and repair or replace as necessary.

6.7.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
INOPERABLE – LIGHT FIXTURE
LIVING ROOM

The light fixture did not operate when the switch was turned on. Try replacing the bulb first. A qualified contractor should evaluate and repair or replace as necessary.

6.8.1 – Stairways & Railings
Stairways & Railings 1
LOOSE – HANDRAIL

At the interior stairs, the handrail was loose.  A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

 7 – Kitchen
7.7.1 – Windows
Windows 1
SCREENS DAMAGED/MISSING
Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.
7.14.1 – Range/Oven/Cooktop
Range/Oven/Cooktop 1
Range/Oven/Cooktop 2
DAMAGED – CONTROL KNOB
The stove/oven knob was damaged and did not operate properly.  A qualified contractor should evaluate and repair or replace as necessary.
 8 – Laundry
8.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION NOT PRESENT

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.4.1 – Ceilings & Walls
Ceilings & Walls 1
SIGNS OF REPAIR-WALLS
The walls had signs of a previous repair.  A qualified contractor should evaluate and repair or replace as necessary.
9.9.1 – Cabinets & Counters
Cabinets & Counters 1
GROUT – BACKSPLASH/WALL
The tile on the wall or backsplash had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.
 10 – Bathroom 2
10.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
NOT WORKING – SINK STOPPER

The drain stop did not work or did not hold water in the sink.  A qualified contractor should evaluate and repair or replace as necessary.

 12 – Plumbing
12.7.1 – Sump Pit
Sump Pit 1
NOT RESPONDING

The property had a sump pump. The sump pump did not respond to the controls. A qualified contractor should evaluate and repair/replace as necessary.

This system protects the property from water intrusion by discharging rising groundwater or seepage from surface runoff to the exterior of the property or to a waste pipe or storm drain. Sump pumps require periodic maintenance to ensure that they work when they’re needed and should be tested on an annual basis to ensure they are in working order. The pumps can be tested by lifting the float, but to avoid potential shock/electrocution hazard testing should be performed using a tool which will not conduct electricity. Pumps have a filter that should be cleaned during routine maintenance.

 14 – Water Heating Equipment
14.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE HIGH

The water temperature was higher than the acceptable range of 120-130 degrees. We recommend adjusting the water heater thermostat.

 15 – Heating
15.7.1 – Condensate
Condensate 1
SECONDARY

The secondary drain line was capped or not routed to a drain. If the primary drain line becomes blocked, this condition could cause condensation to not drain properly and possibly damage the unit. The inspector recommends installing a secondary drain or installing an over flow protection device. A qualified contractor should evaluate then repair or replace as advised.

 17 – Structural Basement
17.9.1 – Electrical in Basement
Electrical in Basement 1
DEFECT – LIGHT FIXTURE
Light fixtures in basement not working and/or missing bulbs at time of inspection. Recommend a qualified contractor evaluate and repair a replace as needed.
17.9.2 – Electrical in Basement
Electrical in Basement 1
OUTLET MISSING FACEPLATE
Outlet box was missing a cover plate. A qualified contractor should evaluate and repair or replace as necessary.