2 – Roof
2.2.1 – Roof Covering
Roof Covering 1
Roof Covering 2
DAMAGED/DETERIORATED

The roof covering material was damaged/deteriorated in some areas.  A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

2.2.2 – Roof Covering
Roof Covering 3
STAINED SHINGLES

The inspector observed stains on the shingles in areas. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

 4 – Exterior
4.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
CRACKING – MINOR

Siding showed cracking and or damage in one or more places. Recommend monitoring, and if the problem exacerbates, a qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.4.2 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 2
INADEQUATE ROOF CLEARANCE

The siding was in direct contact with the roof covering materials in some areas at the time of inspection. This condition can cause deterioration of the bottom edge of the siding at these locations. Ideally, there should be a minimum clearance of at least 1 1/2 inches from the bottom of the siding material to the top of the roof covering material. Recommend further evaluation by a qualified contractor to repair or replace.

4.4.3 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 3
LIFTED NAILS

The siding/trim has lifted nails and needs tightened.

Recommend a qualified contractor should evaluate and repair or replace as needed.

4.4.4 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 4
LOOSE – SIDING

The exterior wall-covering material was loose in one or more areas.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.8.1 – Electrical Outlets
Electrical Outlets 1
MISSING WEATHERPROOF COVERING
THROUGHOUT PROPERTY

The exterior electrical outlet was missing an in-use weatherproof covering. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.8.2 – Electrical Outlets

Electrical Outlets 2

Electrical Outlets 2

NOT WORKING
THROUGHOUT PROPERTY

An exterior electrical outlet was not working. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.9.1 – Windows
Windows 1
DAMAGED – SCREEN
2ND FLOOR BACK

One or more window screens were damaged or deteriorated.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
VINES ON SIDING

Vegetation growing on siding should be removed and kept away from eaves, woodwork, doors, chimneys, or other building components. They hold moisture against the wall, hide rot and other problems and are conducive conditions for termites, carpenter ants,  etc. The growth does not allow full inspection of the siding and can hide potential defects underneath.

Recommend a qualified contractor evaluate and repair or replace as necessary.

4.14.1 – Exterior Faucets (Hose Bibs)
Exterior Faucets (Hose Bibs) 1
DAMAGED/LOOSE KNOB
LEFT SIDE

The outside water faucet has a damaged, missing or loose knob. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.19.1 – Decks & Balconies
Decks & Balconies 1
Decks & Balconies 2
CONTACT WITH GROUND

A wood support post or wood portion of the deck was in direct contact with the ground/dirt. The wood should be pressure treated and ideally be: placed in a metal bracket and/or cement casing, and have clearance from the ground level. Wood in direct contact with dirt will wick up ground moisture and deteriorate at an accelerated rate if routine maintenance is not kept.

Recommend a qualified contractor evaluate and repair or replace as needed.

4.19.2 – Decks & Balconies
Decks & Balconies 3
MISSING – LEDGER FLASHING
FRONT

Flashing was missing at the ledger board. This flashing problem may allow water to enter into the wall cavity or building components. A qualified contractor should evaluate and repair or replace as necessary.

4.19.3 – Decks & Balconies
Decks & Balconies 4
PEELING PAINT – DECK

The exterior deck floor and/or other components were peeling paint. A qualified contractor should evaluate and repair or replace as necessary.

4.20.1 – Railings & Handrails
Railings & Handrails 1
MISSING – HANDRAIL
A stairway of more than 3 steps or drop of over 30″ was missing a handrail.

4.21.1 – Roof Drainage – Downspouts & Extensions

Roof Drainage - Downspouts & Extensions 1
EXTENSIONS TOO SHORT

One or more down spout extensions were too short. Recommend installing 6-8ft long (or greater as needed) extensions to divert rainwater runoff away from the property.

 5 – Attached Garage
5.2.1 – Occupant Door
Occupant Door 1
NOT FIRE RATED

The inspector was unable to verify that the door was fire rated . This may be considered a fire safety hazard. The door between the garage and the house should be a solid wood door at least 1-3/8 inches thick, a solid or honeycomb-core steel door at least 1-3/8 inches thick, or a 20-minute fire-rated door. This means that should a fire occur in garage, the occupant door does not afford protection until firemen arrive. A qualified contractor should evaluate and repair or replace as necessary.

5.3.1 – Occupant Door 2
Occupant Door 2 1
NOT FIRE RATED

The inspector was unable to verify that the door was fire rated . This may be considered a fire safety hazard. The door between the garage and the house should be a solid wood door at least 1-3/8 inches thick, a solid or honeycomb-core steel door at least 1-3/8 inches thick, or a 20-minute fire-rated door. This means that should a fire occur in garage, the occupant door does not afford protection until firemen arrive. A qualified contractor should evaluate and repair or replace as necessary.

5.4.1 – Ceiling, Walls & Firewalls
Ceiling, Walls & Firewalls 1
FIREWALL BREAK – CEILING

An opening was in the drywall or gypsum board ceiling of the garage.

The ceiling to separate the garage and the living areas, or shared attic space with living areas, should be fire-rated. This ceiling must be covered with at least 1/2-inch thick (and preferably 5/8-inch thick Type X) gypsum board or equivalent applied to the garage side.

Recommend a qualified contractor evaluate and repair and seal all openings as necessary.

5.6.1 – Vehicle Door
Vehicle Door 1
Vehicle Door 2
MISSING SPRING CONTAINMENT

The garage door was missing spring containment at the time of inspection. Extension springs should be contained by a cable that runs through the center of the springs. If a spring breaks, containment helps to prevent broken parts from flying around dangerously in the garage.  Recommend a qualified contractor evaluate and repair or replace as needed.

5.7.1 – Door Opener
Door Opener 1
EXTENSION CORD USED

An extension cord was being used to power the garage door operator. Extension cords are for temporary use only, and the operator should be plugged into a dedicated outlet. Recommend a qualified contractor evaluate and update to current building standards as necessary.

5.8.1 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 1
GFCI – NOT ALL PROTECTED

Ground Fault Circuit Interrupter (GFCI) protection was not provided for all the garage electrical outlets. A qualified contractor should evaluate and implement according to current standards.

Although GFCI protection of garage circuits may not have been required at the time in which this property was built, GFCI protection is now required for all 15- and 20-amp receptacles in a garage, including outlets for refrigerators, sprinkler systems, garage door openers, and washing machines – some items may not be protected on purpose due to the potential for them to go unnoticed and cause damage.

5.8.2 – Electrical Outlets & Fixtures
Electrical Outlets & Fixtures 2
Electrical Outlets & Fixtures 3
Electrical Outlets & Fixtures 4
MISSING – FACEPLATE
GARAGE

An outlet or switch box in the garage was missing a faceplate cover. This may be a shock hazard. Recommend a qualified contractor install the missing piece.

 6 – Interior, Doors, Windows
6.5.1 – Windows

Windows 1

Windows 2
Windows 3
BROKEN SEALS

The window appeared to have a broken seal that has been compromised.  Condensation and/or cloudiness between the two panes of glass was observed.  This will have a negative impact on energy efficiency.  Also, because there is moisture between the panes with no ventilation, mold can eventually develop.  A qualified contractor should evaluate and repair or replace as necessary.

6.6.1 – Electrical Outlets
Electrical Outlets 1
NOT GROUNDED – OUTLET
DINING ROOM

One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.

6.7.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
NOT WORKING – BULB(S)
DINING ROOM

One or more light bulbs were not working at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as needed.

 7 – Kitchen
7.7.1 – Windows
Windows 1
STUCK SHUT
KITCHEN

The window had a sash that was unable to be opened without excessive force, possibly from being painted or nailed shut.  A qualified contractor should evaluate and repair or replace as necessary.

7.13.1 – Dishwasher
Dishwasher 2
DIRTY – DRAIN LINE

The dishwasher drain line was dirty and/or possibly clogged at the time of inspection. This may be related to the lack of a “high loop” in the drain line. A high loop in the drain hose is to keep water from settling in the hose to prevent any odors from backing up into the dishwasher. A smell or mold may appear if not corrected. Recommend a qualified contractor evaluate and repair or replace as needed.

7.13.2 – Dishwasher
Dishwasher 2
NO HIGH LOOP

The dishwasher drain line came out from a low location and did not discharge into a higher drain pipe. Dishwasher drain lines require a “high loop” in the line in order to drain properly. A “high loop” may have been hidden behind the appliance itself. The high loop in the drain hose is to keep water from settling in the hose to prevent any odors from backing up into the dishwasher. Food or debris may become stuck in the line and smell or mold if not corrected. Recommend a qualified contractor evaluate and repair or replace as needed.

 8 – Laundry
8.4.1 – Exhaust Fan
Exhaust Fan 1
NOT WORKING
LAUNDRY AREA

The laundry area exhaust fan did not work.  A qualified contractor should evaluate and repair or replace as necessary.

8.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION NOT PRESENT

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.2.1 – Doors
Doors 1
NOT CLOSING TIGHT
PRIMARY BATHROOM

The door needs a strike plate adjustment to close tightly.

9.6.1 – Windows
Windows 1
DAMAGED FRAME
PRIMARY BATHROOM

A window had a damaged frame at an interior area.  A qualified contractor should evaluate and repair or replace as necessary.

9.6.2 – Windows
GLASS BROKEN/CRACKED

The window had a cracked or broken glass pane.  A qualified contractor should evaluate and repair or replace as necessary.

9.6.3 – Windows
Windows 2
SCREENS DAMAGED/MISSING
PRIMARY BATHROOM

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

9.7.1 – Electrical Outlets
Electrical Outlets 1
DID NOT TRIP – GFCI OUTLET

A GFCI outlet was defective (did not trip when tested). A qualified contractor should evaluate and repair or replace as necessary.

9.14.1 – Tub, Shower Area
Tub, Shower Area 1
MISSING/DAMAGED GROUT

Tiles on the wall in the bath/shower area had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.

9.18.1 – Whirlpool/Jetted Bathtub
Whirlpool/Jetted Bathtub 1
DIRTY

Inspection of the Whirlpool jetted bathtub is beyond the scope of the property inspection. The bathtub was filled and turned on using normal operating controls as a courtesy to the client. When operating the jetted tub, debris was dislodged from the jets. A qualified contractor should evaluate and repair or replace as necessary.

 10 – Bathroom 2
10.6.1 – Windows
Windows 1
SCREENS DAMAGED/MISSING
1ST FLOOR HALL BATHROOM

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

10.9.1 – Cabinets & Counters
Cabinets & Counters 1
CAULKING – BACK SPLASH

The counter top needs caulking with silicone along the back splash.  A qualified contractor should evaluate and repair or replace as necessary.

10.16.1 – Water Supply Functional Flow
Water Supply Functional Flow 1
Water Supply Functional Flow 2
WEAK VOLUME/PRESSURE

The shower/bathtub faucet was weak in volume and/or pressure.  A qualified contractor should evaluate and repair or replace as necessary.

 11 – Bathroom 3
11.3.1 – Exhaust Fan
Exhaust Fan 1
NOT WORKING

The bathroom exhaust fan did not work.  A qualified contractor should evaluate and repair or replace as necessary.

11.16.1 – Water Supply Functional Flow
Water Supply Functional Flow 1
WEAK VOLUME/PRESSURE

The shower/bathtub faucet was weak in volume and/or pressure.  A qualified contractor should evaluate and repair or replace as necessary.

 13 – Electrical
13.8.1 – Sub-Panel
Sub-Panel 1
Sub-Panel 2
MISSING – CIRCUIT LABELS

The circuit labels were missing, partial, or illegible at the electrical distribution panel. The circuit labels provide information describing the locations each individual circuit breaker provides power too.

Recommend a qualified contractor verify the breakers and accuracy of any existing labeling as necessary.

13.8.2 – Sub-Panel
Sub-Panel 3
OPEN KNOCKOUTS – PANEL

The sub panel was missing covers for open knockouts. Qualified electrician should investigate and repair or replace as necessary.

13.9.1 – Sub-Panel 2
Sub-Panel 2 1
Sub-Panel 2 2
MISSING – CIRCUIT LABELS

The circuit labels were missing, partial, or illegible at the electrical distribution panel. The circuit labels provide information describing the locations each individual circuit breaker provides power too.

Recommend a qualified contractor verify the breakers and accuracy of any existing labeling as necessary.

 14 – Water Heating Equipment
14.2.1 – Water Shut-Off
Water Shut-Off 1
CORRODED – VALVE

The water heating equipment had a cold water supply shutoff valve installed. The shut-off valve was corroded. The valve was not operated during the inspection. A qualified contractor should evaluate and repair or replace as necessary.

14.9.1 – Exterior Condition/Leakage
Exterior Condition/Leakage 1
WATER STAINS

There are water stains around the water heater that appear to be from the unit. This may be due to: an active leak in the tank or it’s pipe connections, excessive condensation, or the unit’s age. Recommend a qualified contractor evaluate and repair or replace as necessary.

14.10.1 – Drain Valve & Drip Pan
Drain Valve & Drip Pan 1
DRAIN VALVE CAP

The drain valve had a cap or connection, which may be a sign the valve is leaking. Further evaluation and monitoring are recommended. Recommend asking the current home owner for more information about this and any known issues. Should the valve be leaking a qualified contractor should repair or replace it as needed.

14.12.1 – Operation & Response to Controls
Operation & Response to Controls 1
FLAMES

Flames were not entirely burning a blue color. Orange and yellow flames may be an indicator the fuel-air mixture is not right and gas may not be burning as efficiently as possible. Recommend a qualified contractor evaluate to adjust, repair, or replace fuel-burning components as necessary.

 15 – Heating
15.10.1 – Blower
Blower 1
BLOWER WHEEL DIRTY

The blower motor and/or wheel appeared to be dirty at the time of inspection. Blower fan motors and fan wheels are subjected to constant dirt, dust, and lint and can become overly dirty when not cleaned on a regular basis and even faster if the air filters are not changed regularly.

A qualified contractor should evaluate, clean, and service as necessary, and certify the unit is in good working order.

15.12.1 – Heating System Ignition & Operation
SHORT CYCLING

The furnace was short-cycling (repeated start-up and shut-down within minutes of each other) at the time of the inspection. Most systems should run about 2-3 cycles per hour. A qualified contractor should evaluate and repair or replace as necessary.

15.12.2 – Heating System Ignition & Operation
Heating System Ignition & Operation 1
DIRTY

The heating system did fire and appeared to be in serviceable condition at the time of the inspection. However, the interior of the cabinet was dirty. Cleaning, servicing and/or certification of the HVAC system by a qualified contractor is recommended and repaired or replaced as necessary.

15.12.3 – Heating System Ignition & Operation
Heating System Ignition & Operation 2
FLAMES

The heating system did fire and appeared to be in serviceable condition at the time of the inspection. However, the appearance of the flames during operation indicated that gas combustion was not correct. Cleaning, servicing and/or certification of the HVAC system by a qualified contractor is recommended and repaired or replaced as necessary.

 16 – Cooling
16.2.1 – AC Refrigerant Lines
AC Refrigerant Lines 1
DAMAGED INSULATION

The air-conditioner refrigerant suction line (large, insulated) has damaged or missing insulation in areas. A qualified contractor should evaluate and repair/replace as necessary.

16.3.1 – AC Compressor
AC Compressor 1
AC Compressor 2
UNIT IS NOT LEVEL

The exterior compressor unit was not level. Over time, this may result in noisy fan operation, damage to the fan bearings and a shortened fan lifespan, or it may result in movement of the compressor housing which can cause leaks in refrigerant lines resulting in expensive service. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 17 – Structural Basement
17.4.1 – Basement Interior Wall Structure
Basement Interior Wall Structure 1
BASEMENT WALLS NOT FLOATING

Basement walls were not constructed using a method which will allow for soil movement. This method is usually termed “floating” the walls and involves leaving a gap at the bottom of the wall so that vertical movement (heaving) of the concrete slab basement floor will not be transmitted to the rest of the property structure. Colorado has areas with expansive soils. Expansive soils are soils which increase to many times their original volume in response to increases in soil moisture content, creating forces which can easily damage property structural components such as foundations, floor slabs, flat work and interior and exterior wall coverings. Consider consulting with a qualified contractor before the expiration of your Inspection Objection Deadline to discuss options and costs for correction an/ or stabilization.

17.5.1 – Moisture Intrusion
Moisture Intrusion 1
WATER DAMAGE AROUND PLUMBING

Water damage was visible in the crawlspace floor structure around plumbing lines. There may be a past or current leak in the nearby drain or supply lines that could further stain or rot wood if not corrected.

17.9.1 – Electrical in Basement
Electrical in Basement 1
JUNCTION BOX MISSING COVER PLATE
Splice/Junction box was missing a cover plate. A qualified contractor should evaluate and repair or replace as necessary.