4 – Exterior – Condo/Townhome
4.1.1 – Exterior Doors
Exterior Doors 1
NOT LOCKING

The locking hardware is damaged or not installed properly and the door isn’t able to be locked. Recommend a qualified contractor to evaluate and repair or replace as needed.

 7 – Interior, Doors, Windows
7.2.1 – Ceilings & Walls
Ceilings & Walls 1
ASBESTOS CEILING

The property had ceiling materials that may contain asbestos. Ceiling tiles or popcorn textures were manufactured or installed using asbestos as late as the early 90s.

In the past, asbestos fibers were added during production to strengthen and increase durability. Materials that contain asbestos, when intact and in good condition, are generally considered non-friable and not hazardous. Heat, water, weathering, or aging can weaken asbestos materials to the point where it is considered friable. Friable material includes any material containing more than 1 percent asbestos that can be crumbled, pulverized, or reduced to powder with hand pressure. This includes previously non-friable material which has been damaged to the extent that it may be crumbled, pulverized, or reduced to powder by hand pressure and can also be made friable during its removal. Friable materials can release asbestos fibers into the air. Once in the air, asbestos fibers present a health hazard to people who inhale those fibers.

7.2.2 – Ceilings & Walls
Ceilings & Walls 2
MINOR CRACKS-CEILING
GUEST CLOSET

Minor cracking was visible on the interior ceilings.  A qualified contractor should evaluate and repair or replace as necessary.

7.2.3 – Ceilings & Walls
Ceilings & Walls 3
SIGNS OF REPAIR-CEILINGS
PRIMARY CLOSET

The interior ceilings have signs of repairs. Recommend asking the current homeowner for more information. Recommend further evaluation from a qualified contractor should the repairs be excessive or of visibly poor quality.

7.4.1 – Doors
Doors 1
MISSING – DOORSTOP

The door had a damaged or missing doorstop.  A qualified contractor should evaluate and repair or replace as necessary.

7.9.1 – Smoke & CO Detectors
Smoke & CO Detectors 1
Smoke & CO Detectors 2
SMOKE DETECTOR MISSING
BEDROOMS

The smoke detector was missing. A qualified person should replace them as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of the date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.

 8 – Kitchen
8.6.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION

No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

8.8.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
INOPERABLE

The light fixture did not operate when the switch was turned on. Try replacing the bulb first. A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.7.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

9.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
CLOGGED/SLOW – SINK DRAIN

The sink drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.

9.10.2 – Drain Waste and Vent System
Drain Waste and Vent System 2
NOT WORKING – SINK STOPPER

The drain stop did not work or did not hold water in the sink.  A qualified contractor should evaluate and repair or replace as necessary.

9.14.1 – Tub, Shower Area
Tub, Shower Area 1
CRACKED/DAMAGED – SHOWER

The shower has minor cracking or damage.  A qualified contractor should evaluate and repair or replace as necessary.

9.15.1 – Fixture Valve Installation And Temperature
Fixture Valve Installation And Temperature 1
WATER NOT HOT

The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.

The hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.

Recommend a qualified contractor to evaluate and repair or replace as necessary.

 10 – Bathroom 2
10.2.1 – Doors
Doors 1
NOT LOCKING

The door did not lock properly.  A qualified contractor should evaluate and repair or replace as necessary.

10.2.2 – Doors
NOT OPERATE SMOOTHLY

The door did not operate smoothly.  A qualified contractor should evaluate and repair or replace as necessary.

10.7.1 – Electrical Outlets
Electrical Outlets 1
DID NOT TRIP – GFCI OUTLET

A GFCI outlet was defective (did not trip when tested). A qualified contractor should evaluate and repair or replace as necessary.

10.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
FLEX PIPE

Flexible drain lines can clog, leak, or fail. Flex lines design includes multiple folds in which moisture may become trapped and mold may grow.  A qualified contractor should evaluate and repair or replace as necessary.

10.15.1 – Fixture Valve Installation And Temperature
Fixture Valve Installation And Temperature 1
WATER NOT HOT

The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.

The hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.

Recommend a qualified contractor to evaluate and repair or replace as necessary.

 12 – Electrical
12.2.1 – Distribution Panels
Distribution Panels 1
FPE FEDERAL PACIFIC PANEL

The main electrical distribution panel is a Federal Pacific Electric (FPE) panel. These panels have a reputation for being problematic and further evaluation by a qualified electrician is recommended. FPE panel breakers are known to fail to trip at a much higher rate than standard panels. When a breaker fails to trip, the breaker and other components, including wires, may overheat and melt. The panel itself could overheat and catch fire.

Due to safety concerns, no further evaluation was conducted on this panel.  A qualified contractor should evaluate and replace as necessary.

 15 – Cooling – Window/Wall AC
15.1.1 – System Information
System Information 1
DAMAGED – COIL FINS