4 – Exterior – Condo/Townhome
4.1.1 – Exterior Doors
Exterior Doors 1
RUBS FRAME

An entry door rubs at the door frame when closing. This may mean the door or frame is out of the square or that hinges may not be installed properly.

A qualified contractor should evaluate and repair or replace as necessary.

 5 – Detached Garage
5.5.1 – Floor
Floor 1
CRACKED – COMMON

The concrete floor in the garage was cracked.

A qualified contractor should evaluate and repair as necessary.

5.6.1 – Vehicle Door
Vehicle Door 1
DAMAGE – PANELS

The garage door paneling was dented, corroded, or damaged and should be further evaluated by a qualified contractor to repair or replace it as needed.

 6 – Interior, Doors, Windows
6.4.1 – Doors

Doors 1

MISSING – HARDWARE

The door was missing hardware and would not latch.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows

Windows 1

LOCK DAMAGED/MISSING

The window had damaged or missing lock hardware.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.2 – Windows

Windows 1

Windows 2

SCREENS DAMAGED/MISSING

Some windows had damaged or missing screens.  A qualified contractor should evaluate and repair or replace as necessary.

6.6.1 – Electrical Outlets
LOOSE CONTACTS – OUTLET
PATIO

An electrical outlet had loose contacts and no longer holds a plug securely. A qualified contractor should evaluate and repair or replace as necessary.

6.6.2 – Electrical Outlets

Electrical Outlets 1

NOT GROUNDED – OUTLET

One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.

6.7.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
INOPERABLE – LIGHT FIXTURE

The light fixture did not operate when the switch was turned on. Try replacing the bulb first. A qualified contractor should evaluate and repair or replace as necessary.

 8 – Kitchen
8.2.1 – Doors
Doors 1
PEELING PAINT

The door had areas of peeling paint.  A qualified contractor should evaluate and repair or replace as necessary.

8.4.1 – Floors
Floors 1
CRACKED/DAMAGED TILE

The tile floor was cracked/damaged.  A qualified contractor should evaluate and repair or replace as necessary.

8.5.1 – Cabinets & Counters
Cabinets & Counters 1
MOISTURE STAIN

The inspector observed moisture stains on the wall at the sink base. A qualified contractor should evaluate, then repair or replace as advised.

8.6.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION

No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

8.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
FLEX PIPE

The sink drain line had a flex pipe used as part of the drain line. Flexible drain lines can smell, clog, leak or fail. Flex lines design includes multiple folds in which moisture may become trapped and mold may grow.  A qualified contractor should evaluate and repair or replace as necessary.

8.12.1 – Food Waste Disposer
LEAKS

The food waste disposer was leaking at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

8.12.2 – Food Waste Disposer
Food Waste Disposer 1
NOT WORKING

The food waste disposer was not working at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

8.13.1 – Dishwasher
Dishwasher 1
DOOR HITS CABINET

The dishwasher door hits the cabinet when opening/closing. A qualified contractor should evaluate, then repair or replace as advised.

8.15.1 – Range Hood
Range Hood 1
THE LIGHT DID NOT WORK

The vent hood light was not working at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

8.17.1 – Refrigerator
Refrigerator 1
NOT COOLING PROPERLY

The refrigerator/freezer was not cooling at proper temperatures.  It is recommended that a refrigerator cools at around 38 degrees while a freezer cools at around zero degrees.  A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.5.1 – Floors
Floors 1
MISSING/DAMAGED GROUT

The tile floor had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.

9.7.1 – Electrical Outlets
Electrical Outlets 1
NO GFCI PROTECTION

No ground fault circuit interrupter (GFCI) protection was provided for the bathroom electrical outlets. Although GFCI protection of bathroom circuits may not have been required at the time of in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing bathroom electrical circuits to provide GFCI protection. This can be achieved by:

1. Replacing the current standard outlets with GFCI outlets.

2.  Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet

3.  Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.

A qualified contractor should evaluate and repair or replace as necessary.

9.8.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
INSTALL

The light fixture was installed improperly. It was not level. A qualified contractor should evaluate, then repair or replace as advised.

9.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
CLOGGED/SLOW – SINK DRAIN

The sink drain line was clogged or drains slowly. A qualified contractor should evaluate and repair or replace as necessary.

9.14.1 – Tub, Shower Area
Tub, Shower Area 1
CAULK – TUB TOP

The tub/shower area had deteriorated or missing sealant (caulking or grout) where the shower wall rests on the tub and/or at the inside corners. A qualified contractor should evaluate and repair or replace as necessary.

 11 – Central Water Heating
11.1.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE LOW

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace it as necessary.

 12 – Electrical
12.2.1 – Distribution Panels
Distribution Panels 1
MISSING – MANUFACTURERS LABEL

The manufacturer’s label was missing, partial, or illegible on the electrical service panel. The manufacturer’s label typically provides information describing the main panel such as the name of the panel manufacturer, the panel model number, the panel amperage rating, limitations related to the environment in which the panel was designed to be installed, and grounding/bonding information for that particular model. The Inspector was unable to confirm the existence of proper conditions when confirmation would require information taken from this missing label.

12.2.2 – Distribution Panels
Distribution Panels 2
OLDER/OBSOLETE PANEL

The inspector observed an older/obsolete panel. While there are no known inherent defects, the inspector recommends the panel be evaluated by a licensed electrician.