2 – Attic, Insulation, and Ventilation
2.3.1 – Attic Moisture Intrusion
Attic Moisture Intrusion 1
WATER INTRUSION – STRUCTURE

Visible signs of water intrusion in the attic are present on rafters, trusses, or the roof decking. Water intrusion can lead to more costly repairs and increase damage if not corrected. The extent of intrusion or how often it occurs could not be determined. A qualified contractor should evaluate and repair or replace as necessary.

 

 4 – Attached Garage
4.5.1 – Vehicle Door
Vehicle Door 1
DAMAGE – PANELS

The garage door paneling was dented, corroded, or damaged and should be further evaluated by a qualified contractor to repair or replace it as needed.

 5 – Interior, Doors, Windows
5.4.1 – Doors
Doors 1
Doors 2
MISSING – DOORSTOP

The door had a damaged or missing doorstop.  A qualified contractor should evaluate and repair or replace as necessary.

5.5.1 – Windows
Windows 1

Windows 2

BROKEN SEALS
DINING ROOM

The window appeared to have a broken seal that has been compromised.  Condensation and/or cloudiness between the two panes of glass were observed.  This will have a negative impact on energy efficiency.  Also, because there is moisture between the panes with no ventilation, mold can eventually develop.  A qualified contractor should evaluate and repair or replace as necessary.

5.5.2 – Windows
Windows3
Windows 4
Windows 5
SEALANT DAMAGED AROUND FRAME

The sealant was damaged and deteriorated around the window. Recommend a qualified contractor to repair or replace as necessary.

5.7.1 – Electrical Fixtures & Switches

Electrical Fixtures & Switches 1

Electrical Fixtures & Switches 2

NOT WORKING – BULB(S)

One or more light bulbs were not working at the time of inspection. Recommend a qualified contractor to evaluate and repair or replace as needed.

5.9.1 – Smoke & CO Detectors

Smoke & CO Detectors 1

THE SMOKE DETECTOR IS NOT SECURED

The smoke detector was not secured properly to the ceiling/wall. A qualified person should repair or replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of the date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.

 7 – Kitchen
7.7.1 – Windows

Windows 1

BROKEN SEALS

The window appeared to have a broken seal that has been compromised.  Condensation and/or cloudiness between the two panes of glass were observed.  This will have a negative impact on energy efficiency.  Also, because there is moisture between the panes with no ventilation, mold can eventually develop.  A qualified contractor should evaluate and repair or replace as necessary.

7.8.1 – Electrical Fixtures & Switches

Electrical Fixtures & Switches 1

NOT WORKING – BULB

A fixture or bulb was not responding to switches at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.

7.9.1 – Faucets Fixtures
Faucets Fixtures 1
SPRAYER NOT WEIGHTED

The sink sprayer was not properly weighted and did not return to the sink on its own. The sprayer hose had to be manually fed back down into the sink/counter area. Recommend a qualified contractor to evaluate and repair or replace as needed.

7.16.1 – Mounted Microwave
Mounted Microwave 1
LIGHT NOT WORKING

The microwave light was not working.  A qualified contractor should evaluate and repair or replace as necessary.

 8 – Laundry
8.2.1 – Doors
SWINGS OPEN/CLOSED
LAUNDRY AREA

The door swings open or closed by itself.  A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.3.1 – Exhaust Fan

Exhaust Fan 1

DIRTY

The bathroom exhaust fan was very dirty and possibly clogged.  A qualified contractor should evaluate and repair or replace as necessary.

9.9.1 – Cabinets & Counters
Cabinets & Counters 1
Cabinets & Counters 2
CAULKING – NEEDS TOUCH-UPS
PRIMARY BATHROOM

Caulking at the bathroom counter area was a poor installation, or had areas in poor condition and needs a touch-up. Recommend a qualified contractor to evaluate and repair or replace as needed

9.13.1 – Toilets
LOOSE ON THE FLOOR
PRIMARY BATHROOM

The toilet was loose on the floor. This condition typically is caused by loose bolts or nuts and/or missing floor seals. The loose toilet can result in leaks, water damage, and mold, as well as damage to the toilet, water supply lines, bolts, and drainage pipes. A qualified contractor should evaluate and repair or replace as necessary.

 10 – Bathroom 2
10.2.1 – Doors

Doors 1

MISSING – DOORSTOP

The door had a damaged or missing doorstop.  A qualified contractor should evaluate and repair or replace as necessary.

10.9.1 – Cabinets & Counters

Cabinets & Counters 1

CAULKING – NEEDS TOUCH-UPS

Caulking at the bathroom counter area was a poor installation, or had areas in poor condition and needs a touch-up. Recommend a qualified contractor to evaluate and repair or replace as needed

 15 – Heating
15.7.1 – Condensate
Condensate 1
Condensate 2
SIGNS OF LEAKING

The condensation drain components for the HVAC system were leaking or showing signs of the previous leaking. A qualified contractor should evaluate and repair or replace as necessary.

15.9.1 – Air Filter
Air Filter 1
VERY DIRTY

The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.

15.12.1 – Heating System Ignition & Operation
EXHAUST FAN

The exhaust fan appeared to be noisy at startup.

 16 – Cooling
16.1.1 – Cooling System Information
Cooling System Information 1
LABEL WORN OUT

The manufacturing label on the system was worn out and illegible. This is an indication of old age or prolonged exposure to harsh elements. Recommend a qualified contractor further evaluate and repair or replace.

16.4.1 – AC Service Disconnect
AC Service Disconnect 1
AC Service Disconnect 2
OBSTRUCTED

The cooling unit shut-off was obstructed or otherwise not accessible at the time of inspection. Recommend a qualified contractor evaluate and clear or modify the location as needed.