2 – Roof 
2.2.1 – Roof Covering
EXPOSED NAILS
ROOF

The inspector observed exposed nails on the roof covering in areas. This condition could allow moisture to penetrate the roof component. A qualified contractor should evaluate and repair or replace as necessary.

4 – Exterior 
4.5.1 – Eaves, Soffits & Fascia
Eaves, Soffits & Fascia 1
MISMATCHED STAIN
FRONT ENTRANCE

There was areas of mismatched stain near the main entrance. A qualified contractor should evaluate and repair or replace as necessary.

4.6.1 – Exterior Doors
Exterior Doors 1
DIFFICULT TO SLIDE
UPSTAIRS PRIMARY BEDROOM

The sliding glass or screen door did not operate properly in the upstairs primary bedroom. The door(s) were operated and did not slide smoothly on the track and/or close using normal operating force. A qualified contractor should evaluate and repair or replace as necessary

4.15.1 – Sump Pump Discharge Pipe
Sump Pump Discharge Pipe 1
DISCHARGE TOO CLOSE
EXTERIOR

The sump pump discharge pipe did not terminate far enough away from the foundation. Erosion can continue or become worse if not corrected possibly leading to water intrusion. This condition may cause problems by introducing excessive amounts of moisture to the soil near the foundation. A qualified contractor should evaluate and install a proper extension, to properly route drainage away from the foundation, usually at least 6 feet. A qualified contractor should evaluate and repair or replace as necessary.

4.21.1 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 1
EXTENSIONS NOT POSITIONED PROPERLY
EXTERIOR

One or more downspout extensions were not properly positioned. Extensions should be properly attached with a proper slope to guide run-off 5 feet away from the foundation structure. A qualified contractor should evaluate and repair or replace as necessary.

6 – Interior, Doors, Windows
6.3.1 – Floors
Floors 1
DAMAGED – FLOOR COVERING
UPSTAIRS HALLWAY

There appeared to be some damage to the interior flooring in areas in the upstairs hallway. A qualified contractor should evaluate and repair or replace as necessary.

6.4.1 – Doors
MISSING – HANDLE/KNOB
MECHANICAL ROOM

The door was missing a handle or knob at the mechanical room. A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows
Windows 1
Windows 2
SCREENS-MISSING
INTERIOR

All windows and doors had missing screens at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

6.10.1 – Installed Heat Source
Installed Heat Source 1
NO HEAT – SPACE HEATER
CRAWLSPACE

The space heater in the crawlspace was not working at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.

7 – Kitchen 
7.14.1 – Range/Oven/Cooktop
Range/Oven/Cooktop 1
GAS VALVE OFF
OVEN

The gas valve to oven was turned off at the time of inspection. There was an adhesive stuck to the valve and it could not be turned on to operate the oven. A qualified contractor should evaluate and repair or replace as necessary.

9 – Bathroom 2 
9.4.1 – Ceilings & Walls
Ceilings & Walls 1
DAMAGED – WALLS
GUEST BATHROOM

The walls showed signs of minor damage and wear in the guest bathroom. A qualified contractor should evaluate and repair or replace as necessary.

9.9.1 – Cabinets & Counters
Cabinets & Counters 1
CAULKING – BACK SPLASH
GUEST BATHROOM

The counter top needs caulking with silicone along the back splash in the guest bathroom.  A qualified contractor should evaluate and repair or replace as necessary.

10 – Bathroom 3 
10.5.1 – Floors
Floors 1
FLOOR NOT SEALED AT EDGE
HALL BATHROOM

The floor covering was not sealed properly at the edges and may allow moisture intrusion in the guest bathroom.  A qualified contractor should evaluate and repair or replace as necessary.

11 – Bathroom 4 
11.2.1 – Doors
Doors 1
MISSING – STRIKE PLATE
1/2 BATHROOM

The door was missing a strike plate at the door jamb in the 1/2 bathroom. A qualified contractor should evaluate and repair or replace as necessary.

13 – Plumbing EDIT SECTION
13.7.1 – Sump Pit
Sump Pit 1
Sump Pit 2
NOT RESPONDING
SUMP PUMP

The property had a sump pump. The sump pump did not respond to the controls, as it was plugged into an outlet that had a GFCI that would not reset. A qualified contractor should evaluate and repair or replace as necessary.

This system protects the property from water intrusion by discharging rising groundwater or seepage from surface runoff to the exterior of the property or to a waste pipe or storm drain. Sump pumps require periodic maintenance to ensure that they work when they’re needed and should be tested on an annual basis to ensure they are in working order. The pumps can be tested by lifting the float, but to avoid potential shock/electrocution hazard testing should be performed using a tool which will not conduct electricity. Pumps have a filter that should be cleaned during routine maintenance.

14 – Electrical
14.5.1 – Electrical Circuit Breakers
Electrical Circuit Breakers 1
BREAKER TRIPPING
ELECTRICAL PANEL

The breaker designated for the crawlspace heater was constantly tripping and the crawlspace heater was not operational. A qualified contractor should evaluate and repair or replace as necessary.

15 – Water Heating Equipment 
15.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE LOW
WATER HEATER

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

16 – Heating 
16.6.1 – Cabinet
Cabinet 1
CORRODED, RUSTED, DIRTY
FURNACE

The heating system cabinet was corroded, rusted or dirty/damaged in some areas. A qualified contractor should evaluate and repair or replace as necessary.

17 – Cooling
17.6.1 – Cooling System Operation
Cooling System Operation 1
Cooling System Operation 2
DID NOT PRODUCE COOLED AIR
AC

The cooling system turned on but did not operate as expected by producing adequate conditioned cooled air. An ambient air test was performed to determine if the difference in temperatures of the supply and return air was between 14 degrees and 22 degrees. A qualified contractor should evaluate and repair or replace as necessary.