4 – Exterior 1
4.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
LOOSE – SIDING
The exterior wall-covering material was loose in one or more areas.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.7.1 – Electrical Fixtures
Electrical Fixtures 1
NOT WORKING – BULB
A bulb at an exterior light fixture did not respond to the switch at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary according to current standards.
4.11.1 – Walkways
Walkways 1
SPALLING
The walkway(s) had surface spalling in areas. This condition will continue to degrade if not corrected. A qualified contractor should evaluate and repair or replace as necessary.
4.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
NEGATIVE GRADING
The property had areas of neutral or negative drainage, which will route runoff from precipitation to the foundation.  Excessive moisture content in soil supporting the foundation can cause foundation and other structural damage from undermining, heaving or settling, depending on soil composition, moisture content and other conditions.The ground around the property should slope away from all sides, ideally 6 inches for the first 10 feet from the house foundation perimeter. Downspouts, surface gutters and drains should also be directing water away from the foundation. A qualified contractor should evaluate and repair as necessary according to current standards.
4.21.1 – Roof Drainage – Downspouts & Extensions
Roof Drainage - Downspouts & Extensions 1
DAMAGED – DOWNSPOUTS

Downspouts were damaged in areas of property. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation.  A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

5 – Attached Garage 1
5.6.1 – Door Opener
Door Opener 1
MISSING – LIGHT BULB
The garage door operator unit was missing a light bulb. Recommend a qualified contractor evaluate and repair or replace as needed.
6 – Interior, Doors, Windows 1
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
Ceilings & Walls 2
NAIL POPS-CEILINGS
There were “nail pops” visible on the interior ceilings.  A qualified contractor should evaluate and repair or replace as necessary.
6.3.1 – Floors
Floors 1
CARPET STAINS

The carpet was stained in areas. A qualified contractor should evaluate and repair or replace as necessary.

9 – Bathroom 1 Unit 1
9.2.1 – Doors
Doors 1
NOT LATCHING SECURELY
An interior door door did not latch properly. This may be that it was not shimmed properly at the jamb (too wide) or the strike plate was not in the correct position.

A qualified contractor should evaluate and repair or replace as necessary.

12 – Bathroom 4 Unit 1
12.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
NOT WORKING – STOPPER

The sink was missing the stopper or it did not work properly at the time of the inspection. Recommend a qualified contractor evaluate and repair or replace as needed.

14 – Plumbing 1
14.4.1 – Water Pressure
Water Pressure 1
LOW WATER PRESSURE
The property water supply pressure was measured at the exterior faucet or laundry hose bib. Property water supply pressure was lower than the 40 pounds per square inch (PSI), which is considered inadequate by generally-accepted current standards.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

15 – Water Heating Equipment 1
15.4.1 – Expansion Tank / Valve
Expansion Tank / Valve 1
NOT SECURED
The expansion tank was not properly secured. A qualified contractor should evaluate and repair or replace as necessary.
16 – Heating 1
16.9.1 – Air Filter
Air Filter 1
VERY DIRTY

The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.

19 – Exterior 2
19.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
SEAL GAPS AT INTERSECTIONS
Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.
19.14.1 – Exterior Faucets (Hose Bibs)
Exterior Faucets (Hose Bibs) 1
LEAK – IN WALL
The outside water faucet appear to have a leak from the valve within the wall when the water pressure gauge was attached. However, there was no signs of water on the interior of the home.  A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
19.20.1 – Railings & Handrails
Railings & Handrails 1
GATE – NOT LOCKING

The gate was not locking at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.

20- Attached Garage 2
20.3.1 – Ceiling, Walls & Firewalls
Ceiling, Walls & Firewalls 1
MOISTURE INTRUSION – CEILING

Garage ceiling showed signs of current or past moisture intrusion. Moisture intrusion is visibly noted by the presence of water stains or efflorescence but can not tell whether the issue is active without further water testing.

Recommend a qualified contractor evaluate, and if active, make repairs as necessary to prevent further damage and/or mold.

21 – Interior, Doors, Windows 2
21.2.1 – Ceilings & Walls
Ceilings & Walls 1
Ceilings & Walls 2
Ceilings & Walls 3
DAMAGED – MULTIPLE ITEMS

The ceiling and/or walls showed various signs of minor defects at numerous locations including all or some of the following: damage, cracks, holes, previous repairs, and/or improper repairs. A representative number of pictures were taken to provide an example. Should any of these issues appear excessive we recommend a qualified contractor should evaluate and repair or replace items as necessary.

21.4.1 – Doors
Doors 1
NOT LATCHING SECURELY
PRIMARY BEDROOM

An interior door did not latch properly. This may be that it was not shimmed properly at the jamb (too wide) or the strike plate was not in the correct position.

A qualified contractor should evaluate and repair or replace as necessary.

24 – Bathroom 5 Unit 2
24.14.1 – Tub, Shower Area
Tub, Shower Area 1
MISSING/DAMAGED GROUT
Tiles on the wall in the bath/shower area had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.
 
28 – Plumbing 2
28.5.1 – Drain, Waste, & Vent Systems
Drain, Waste, & Vent Systems 1
LEAKING – DRAIN LINE

The drain pipe was actively leaking from the clean out cap at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

29 – Water Heating Equipment 2
29.4.1 – Expansion Tank / Valve
Expansion Tank / Valve 1
NOT SECURED

The expansion tank was not properly secured. A qualified contractor should evaluate and repair or replace as necessary.

29.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE LOW

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

30 – Heating 2
30.7.1 – Condensate
Condensate 1
Condensate 2
SIGNS OF LEAKING

Although nothing was actively leaking there were signs of a previous leak at the furnace. A qualified contractor should evaluate and repair or replace as necessary.

33 – Exterior 3
33.2.1 – Driveways
Driveways 1
CRACKING – MODERATE

The concrete driveway was moderately cracked. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.

33.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
SEAL GAPS AT INTERSECTIONS

Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.

33.11.1 – Walkways
Walkways 1
SPALLING

The walkway(s) had surface spalling in areas. This condition will continue to degrade if not corrected. A qualified contractor should evaluate and repair or replace as necessary.

34 – Attached Garage 3
34.2.1 – Occupant Door
Occupant Door 1
NOT SELF CLOSING

The door between the garage and the living space failed to close by itself. Modern safety requirements require that the door between the home interior and the garage be self-closing for safety reasons related to fire hazard and toxic fumes. A qualified contractor should evaluate and repair or replace as necessary.

35 – Interior, Doors, Windows 3
35.3.1 – Floors
Floors 1
CARPET STAINS

The carpet was stained in areas. A qualified contractor should evaluate and repair or replace as necessary.

38 – Bathroom 8 Unit 3
38.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
NOT WORKING – STOPPER

The sink was missing the stopper or it did not work properly at the time of the inspection. Recommend a qualified contractor evaluate and repair or replace as needed.

42 – Plumbing 3
42.4.1 – Water Pressure
Water Pressure 1
LOW WATER PRESSURE

The property water supply pressure was measured at the exterior faucet or laundry hose bib. Property water supply pressure was lower than the 40 pounds per square inch (PSI), which is considered inadequate by generally-accepted current standards.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

43 – Water Heating Equipment 3
43.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE LOW

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

44 – Heating 3
44.9.1 – Air Filter
Air Filter 1
VERY DIRTY

The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.

47 – Exterior 4
47.4.1 – Wall-Covering, Flashing & Trim
Wall-Covering, Flashing & Trim 1
SEAL GAPS AT INTERSECTIONS
Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.
47.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
NEGATIVE GRADING
The property had areas of neutral or negative drainage, which will route runoff from precipitation to the foundation.  Excessive moisture content in soil supporting the foundation can cause foundation and other structural damage from undermining, heaving or settling, depending on soil composition, moisture content and other conditions.The ground around the property should slope away from all sides, ideally 6 inches for the first 10 feet from the house foundation perimeter. Downspouts, surface gutters and drains should also be directing water away from the foundation. A qualified contractor should evaluate and repair as necessary according to current standards.
47.20.1 – Railings & Handrails
Railings & Handrails 1
GATE – NOT LATCHING

The gate was not locking properly at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.

52 – Bathroom 11 Unit 4
52.4.1 – Ceilings & Walls
Ceilings & Walls 1
BULGE
The wall was bowed or bulges in areas.  A qualified contractor should evaluate and repair or replace as necessary.
58 – Water Heating Equipment 4
58.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE LOW
The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.
59 – Heating 4
59.9.1 – Air Filter
Air Filter 1
VERY DIRTY

The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.

64 – Interior, Doors, Windows 5
64.3.1 – Floors
Floors 1
CARPET LOOSE
The carpet was loose or baggy and may need to be restretched.  A qualified contractor should evaluate and repair or replace as necessary.
64.4.1 – Doors
Doors 1
SWINGS OPEN/CLOSED
GUEST BEDROOM

The door swings open or closed by itself.  A qualified contractor should evaluate and repair or replace as necessary.

65 – Kitchen 5
65.4.1 – Floors
Floors 1
SEAMS WIDE/INCONSISTENT
The flooring had seams that were wide or inconsistent possibly indication loose flooring or poor installation.  A qualified contractor should evaluate and repair or replace as necessary.
65.12.1 – Food Waste Disposer
Food Waste Disposer 1
NOT WORKING

The food waste disposer was not working at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.

67 – Bathroom 15 Unit 5
67.8.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 1
NOT WORKING – BULB
One or more bulbs was not working in the bathroom at the time of inspection.

Recommend a qualified contractor evaluate and repair or replace as needed.

69 – Bathroom 17 Unit 5
69.8.1 – Electrical Fixtures & Switches
Electrical Fixtures & Switches 2
NOT WORKING – BULB
One or more bulbs was not working in the bathroom at the time of inspection.

Recommend a qualified contractor evaluate and repair or replace as needed.

71 – Plumbing 5
71.4.1 – Water Pressure
Water Pressure 1
LOW WATER PRESSURE
The property water supply pressure was measured at the exterior faucet or laundry hose bib. Property water supply pressure was lower than the 40 pounds per square inch (PSI), which is considered inadequate by generally-accepted current standards.

A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

73 – Heating 5
73.6.1 – Cabinet
Cabinet 1
MISSING LATCH
The cabinet panel cover was missing a latch at the time of inspection. This may allow the panel to fall off easily, add difficulty when removing for service, or add difficulty for attaching the panel tightly. Recommend a qualified contractor evaluate and replace screws as needed.
73.9.1 – Air Filter
Air Filter 1
DIRTY

The HVAC system air filter was dirty. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.

74 – Cooling 5
74.3.1 – AC Compressor
AC Compressor 1
COIL FINS DAMAGED

There was damage to the air-conditioner condenser coil fins. This limits the ability to dissipate heat. Further damage to the coil fins should be avoided in order to maintain cooling system efficiency and avoid problems from overheating of the compressor. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 

74.6.1 – Cooling System Operation
Cooling System Operation 1
Cooling System Operation 2
DID NOT PRODUCE COOLED AIR

The cooling system turned on but did not operate as expected by producing adequate conditioned cooled air. An ambient air test was performed to determine if the difference in temperatures of the supply and return air was between 14 degrees and 22 degrees. A qualified contractor should evaluate and repair/replace as necessary.

76 – Exterior 6
76.2.1 – Driveways
Driveways 1
CRACKING – MODERATE
The concrete driveway was moderately cracked. Cracks that progress to a separation of 1/4″ and more would be an indication of settlement, heaving, or structural problems. Cracks may present a tripping hazard. A qualified contractor should evaluate and repair as necessary.
76.11.1 – Walkways
Walkways 1
Walkways 2
SPALLING
The walkway(s) had surface spalling in areas. This condition will continue to degrade if not corrected. A qualified contractor should evaluate and repair or replace as necessary.
76.12.1 – Vegetation, Grading & Drainage
Vegetation, Grading & Drainage 1
NEGATIVE GRADING
The property had areas of neutral or negative drainage, which will route runoff from precipitation to the foundation.  Excessive moisture content in soil supporting the foundation can cause foundation and other structural damage from undermining, heaving or settling, depending on soil composition, moisture content and other conditions.The ground around the property should slope away from all sides, ideally 6 inches for the first 10 feet from the house foundation perimeter. Downspouts, surface gutters and drains should also be directing water away from the foundation. A qualified contractor should evaluate and repair as necessary according to current standards.
76.14.1 – Exterior Faucets (Hose Bibs)
Exterior Faucets (Hose Bibs) 1
Exterior Faucets (Hose Bibs) 2
LEAK
There was a note on the hose faucet stating not to run it because it leaks A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
78 – Interior, Doors, Windows 6
78.2.1 – Ceilings & Walls
Ceilings & Walls 1
Ceilings & Walls 2
PAINT PEELING
The paint was peeling in areas.  A qualified contractor should evaluate and repair or replace as necessary.
78.3.1 – Floors
Floors 2
SEAMS WIDE/INCONSISTENT

The flooring had seams that were wide or inconsistent possibly indication loose flooring or poor installation.  A qualified contractor should evaluate and repair or replace as necessary.

79 – Kitchen 6
79.5.1 – Cabinets & Counters
Cabinets & Counters 1
DAMAGED – CABINET
The base cabinet was damaged.  A qualified contractor should evaluate and repair or replace as necessary.
79.13.1 – Dishwasher
Dishwasher 1
LEAKED

The dishwasher leaked while going through a normal cycle.  A qualified contractor should evaluate and repair or replace as necessary.

82 – Bathroom 19 Unit 6
82.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
LEAKING
The sink drain pipe was leaking at the time of inspection.  A qualified contractor should evaluate and repair or replace as necessary.
82.12.1 – Plumbing Fixtures
Plumbing Fixtures 1
CRACKED/DAMAGED – SINK
The sink was cracked or damaged.  A qualified contractor should evaluate and repair or replace as necessary.
87 – Water Heating Equipment 6
87.13.1 – Water Temperature
Water Temperature 1
WATER TEMPERATURE LOW

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

88 – Heating 6
88.9.1 – Air Filter
Air Filter 1
VERY DIRTY

The HVAC system air filter was very dirty or clogged. This condition reflects a lack of regular maintenance of the HVAC system. Clogged filters can restrict airflow and increase internal temperatures. A clean air filter will help increase the efficiency and prolong the life expectancy of the heating and cooling system. Due to the damage that can be caused by dirty or clogged coils, recommend replacing the filter, as well as cleaning, servicing, and evaluating the HVAC system by a qualified HVAC professional and repair or replace as necessary.