The property had ceiling materials that may contain asbestos. Ceiling tiles or popcorn texture were manufactured or installed using asbestos as late as the early 90s.
In the past, asbestos fibers were added during the production to strengthen and increase durability. Materials that contain asbestos, when intact and in good condition, is generally considered non-friable and is not hazardous. Heat, water, weathering or aging can weaken asbestos materials to the point where it is considered friable. Friable material includes any material containing more than 1 percent asbestos that can be crumbled, pulverized or reduced to powder with hand pressure. This includes previously non-friable material which has been damaged to the extent that it may be crumbled, pulverized or reduced to powder by hand pressure and can also be made friable during its removal. Friable materials can release asbestos fibers into the air. Once in the air, asbestos fibers present a health hazard to people who inhale those fibers.
The interior walls showed evidence that moisture was entering from behind possibly including damage and deterioration. A qualified contractor should evaluate and repair or replace as necessary.
Evidence of a possible mold like substance was observed on the interior walls and/or ceilings. We did not inspect, test or determine if this growth is or is not a health hazard. The underlying cause is moisture. It is recommended to consult a mold inspector or mold remediation specialist to determine if further action is needed.
The carpet was stained in areas. A qualified contractor should evaluate and repair or replace as necessary.
The door had a broken or cracked glass pane. A qualified contractor should evaluate and repair or replace as necessary.
The sliding/folding door would fall off the track when operated. A qualified contractor should evaluate and repair or replace as necessary.
The light fixture did not operate when the switch was turned on. Try replacing the bulb first. A qualified contractor should evaluate and repair or replace as necessary.
The ceiling fan wobbles when operated and may need to be balanced. A qualified contractor should evaluate and repair or replace as necessary.
Carbon monoxide detectors were not installed within a specified distance of each room lawfully used for sleeping purposes. The inspector recommends installation of carbon monoxide detectors in appropriate locations. Colorado House bill 1091 became effective on July 1, 2009 that requires Carbon Monoxide detectors to be installed in most properties that has a fuel-burning heater or appliance, a fireplace, or an attached garage.
There are no carbon monoxide detectors on the lower or upper level.
The smoke detector was missing. A qualified person should replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.
Some of the smoke detectors appeared to be old and beyond their expected life. A qualified person should repair or replace as needed. The existing smoke detectors were tested if present, but they are only noted as to presence and operation as of date of inspection. Smoke detectors may work today but not work when you need them to work. This is why it is important for you to test them on a regular basis, monthly at least. Smoke detectors are recommended by the U.S. Product Safety Commission to be installed inside each bedroom and adjoining hallway and on each living level of the property and basement level.
Recommend removing!
The floors showed signs of minor damage and wear – particularly in high traffic areas. A qualified contractor should evaluate and repair or replace as necessary.
The base cabinet was damaged. A qualified contractor should evaluate and repair or replace as necessary.
No ground fault circuit interrupter (GFCI) protection was provided for kitchen electrical outlets. Although GFCI protection of kitchen circuits may not have been required at the time in which this property was built, as general knowledge of safe building practices has improved with the passage of time building standards have changed to reflect current understanding. The inspector recommends updating the existing kitchen electrical circuits to provide GFCI protection. This can be achieved by:
1. Replacing the current standard outlets with GFCI outlets.
2. Replacing the first circuit outlet located closest to the main electrical service panel with the GFCI outlet
3. Replacing the breaker currently protecting the electrical circuit that contains these outlets with the GFCI breaker.
A qualified contractor should evaluate and repair or replace as necessary.
The microwave was damaged. A qualified contractor should evaluate and repair or replace as necessary.
The laundry room did not have an exhaust fan or an openable window. A qualified contractor should evaluate, then repair or replace as advised.
The paint was peeling in areas. A qualified contractor should evaluate and repair or replace as necessary.
An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.
Excessive lint was built up behind the dryer area, and in parts of laundry area. The dryer vent connection may have become disconnected and should be reconnected to properly route the dryer exhaust to the exterior. Failure to reconnect the vent may result in unsatisfactory conditions from excessive humidity and lint accumulation in the home. Excessively high humidity can damage home materials or components and may encourage the growth of microbes such as mold. A qualified contractor should evaluate and repair or replace as necessary.
The sink drain stop was missing, damaged or did not operate properly. A qualified contractor should evaluate and repair or replace as necessary.
The bathtub drain stop was damaged, missing or did not operate properly. A qualified contractor should evaluate and repair or replace as necessary.
A shower supply arm was loose in the wall. This will cause caulking/sealant to deteriorate at an accelerated rate and may allow water to enter the wall. Over time, this could potentially put added stress on the plumbing connections and develop a leak. Recommend a qualified contractor evaluate and repair or replace it as necessary.
The shower diverter did not divert all of the water to the shower and a stream of water passed though bathtub spout when the shower was on. A qualified contractor should evaluate and repair or replace as necessary.
The tub spout should be sealed at the wall to prevent moisture intrusion in to the wall component. A qualified contractor should evaluate then repair or replace as advised.
Evidence of a possible mold like substance was observed bath or shower area. We did not inspect, test or determine if this growth is or is not a health hazard. The underlying cause is moisture. It is recommended to consult a mold inspector or mold remediation specialist to determine if further action is needed. Further analysis by a mold remediation specialist is recommended. Axium recommends our premier partner – Mold Removal Express. They can be contacted at 720-464-1555 or online at www.axiuminspections.com/mold-removal-express.
Caulking in the shower/tub area was deteriorated at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.
The water heater was at or beyond its warranty and/or expected life expectancy.
The water heater age was determined by the photo included in this report. According to the U.S. Department of energy, these major appliances are intended to run for between 8 and 12 years. Be advised that every water heater will age differently relative to the following life span factors: water quality, mineral buildup, frequency of flushing, the volume of water utilized, size of the tank, brand, and quality of water heater. Although it was operating at the time of the inspection, the inspector can not determine the remaining life of the water heater.
Fresh air supply is recommended by manufacturers for efficient operation of fuel burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.
The heating system cabinet was corroded, rusted or damaged in some areas. A qualified contractor should evaluate and repair or replace as necessary.
The condensation drain components for the HVAC system were leaking or showed signs of previous leaking. A qualified contractor should evaluate and repair or replace as necessary.
The heating system did fire and appeared to be in serviceable condition at the time of the inspection. However, the interior of the cabinet was dirty. Cleaning, servicing and/or certification of the HVAC system by a qualified contractor is recommended and repaired or replaced as necessary.
Due to the year of manufacture, the cooling system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate to clean, service/repair/replace as necessary, and certify the unit if possible. InterNACHI’s Standard Estimated Life Expectancy Chart for Homes
15 – Structural Crawlspace
The inspector observed signs of a possible active leak in the crawlspace.
There were water stains or water damaged areas in the crawlspace at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.
Water damage was visible in the crawlspace floor structure around plumbing lines. There may be a past or current leak in the nearby drain or supply lines that could further stain or rot wood if not corrected. Connected toilet to unit damaged subfloor.