5964 Longford Wy
Colorado Springs, CO 80908
The vent flashing, used to protect areas of the roof from moisture intrusion, was inadequately sealed at the time of the inspection. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.
Gutters were full of debris or granules in areas and need to be cleaned. The debris in gutters can clog drainage, or be a sign gutters are sloped improperly – Either of which may cause problems by overflowing to introduce excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement.
Debris in gutters can also conceal rust, deterioration or leaks that are not visible until cleaned.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
Siding showed cracking and or damage in one or more places. Recommend monitoring, and if the problem exacerbates, a qualified contractor should evaluate and repair or replace as necessary and according to current standards.
Gaps at intersections of the siding, trim, and door and window openings, as well as any other holes in the siding, should be sealed with an appropriate sealant to prevent water penetration into the wall system. A qualified contractor should evaluate and repair or replace as necessary.
It Wasp nest is present at the time of inspection. Recommend removing by qualified contractor.
Window Well(s) lacked covers and may represent a danger to small children and may trap pests. A qualified contractor should evaluate and repair or replace as necessary.
One or more downspout extensions were not properly positioned. Extensions should be properly attached with a proper slope to guide run-off 5 feet away from the foundation structure.
Recommend a qualified contractor evaluate and repair or replace as necessary.
Downspout(s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.
The door between the garage and the living space failed to close by itself. Modern safety requirements require that the door between the home interior and the garage be self-closing for safety reasons related to fire hazard and toxic fumes. A qualified contractor should evaluate and repair or replace as necessary.
The concrete floor in the garage was cracked. Due to expansive soils, minor cracks are to be expected in the slabs or control joints. Recommend a qualified contractor evaluate and repair or replace as needed.
An interior door rubs at the door frame when closing. This may mean the door or frame is out of square or that hinges may not be installed properly.
A qualified contractor should evaluate and repair or replace as necessary.
One or more light bulbs were not working at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as needed.
The door had a damaged or missing doorstop. A qualified contractor should evaluate and repair or replace as necessary.
The microwave chime was not functioning at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.
Caulking at the bathroom counter area was a poor installation, or had areas in poor condition and needs a touch-up. Recommend a qualified contractor evaluate and repair or replace as needed
The toilet was loose at the tank to toilet connection. A qualified contractor should evaluate and repair or replace as necessary.
The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.
Hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.
Recommend a qualified contractor evaluate and repair or replace as necessary.
One or more bulbs was not working in the bathroom at the time of inspection.
Recommend a qualified contractor evaluate and repair or replace as needed.
Some windows had damaged or missing screens. A qualified contractor should evaluate and repair or replace as necessary.
There was a leak at the shower head connection at the time of inspection. Recommend a qualified contractor evaluate and repair or replace as necessary.
The toilet was loose at the floor. This condition typically is caused by loose bolts or nuts and/or missing floor seals. Loose toilet can result in leaks, water damage, and mold, as well as damage to the toilet, water supply lines, bolts, and drainage pipes. A qualified contractor should evaluate and repair or replace as necessary.
The hot water in the shower did not get over 100 degrees whereas the nearby faucets did. This may indicate that either the mixing valve (safety feature to limit potential scalding) or control cartridge needs adjustment to achieve a hot shower. There may be a more significant issue, that only further evaluation can reveal.
Hot and cold supply was installed correctly and the property’s overall hot water temperature was within an acceptable range.
Recommend a qualified contractor evaluate and repair or replace as necessary.
The supply register supplied no detectable heat at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.
The door had improperly installed door hardware that was not recessed flush with the door and/or jamb. A qualified contractor should evaluate and repair or replace as necessary.
The toilet was loose at the floor. This condition typically is caused by loose bolts or nuts and/or missing floor seals. Loose toilet can result in leaks, water damage, and mold, as well as damage to the toilet, water supply lines, bolts, and drainage pipes. A qualified contractor should evaluate and repair or replace as necessary.
Sharp screws / fasteners we used at the electrical panel cover. This could be potentially hazardous if the screws puncture a live electrical wire. A qualified contractor should evaluate and repair or replace as necessary.
One or more wire appears to be melted from overheating near circuit breakers.
A qualified contractor should evaluate and repair or replace as necessary.
The gas supply line lacked a sediment or drip leg. This condition could allow small particles in the gas supply to enter the mechanical. A qualified contractor should evaluate then repair or replace as advised.
The water temperature was higher than the acceptable range of 120-130 degrees. We recommend adjusting the water heater thermostat.
The gas supply line lacked a sediment or drip leg. This condition could allow small particles in the gas supply to enter the mechanical. A qualified contractor should evaluate then repair or replace as advised.