The roof covering material was damaged/deteriorated in some areas. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.


Some of the shingles appeared to be de-granulated in areas. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

The inspector observed stains on the shingles in areas. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.



The roof covering material was missing in some areas. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.


A roof penetration lacked adequate sealant. This condition could allow moisture to enter the roof and attic systems. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

The inspector observed signs of repair at the time of inspection. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

The vent flashing, used to protect areas of the roof from moisture intrusion, was inadequately sealed at the time of the inspection. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

One or more plumbing vents had a rubber boot flange that was damaged. This condition could allow moisture to penetrate the roof component. A qualified contractor should evaluate, then repair or replace as advised prior to the inspection objection deadline.

Gutters had moderate general corrosion visible. Corrosion is generally a sign of poor sloping or drainage, and continued corrosion will eventually result in leaking gutters.
This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

Gutters were full of debris or granules in areas and need to be cleaned. The debris in gutters can clog drainage, or be a sign gutters are sloped improperly – Either of which may cause problems by overflowing to introduce excessive amounts of moisture to the soil beneath the foundation. Excessive moisture in soil supporting the foundation can affect its ability to support the weight of the structure above and may cause foundation damage from soil movement.
Debris in gutters can also conceal rust, deterioration or leaks that are not visible until cleaned.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

Rusty nails often signal excess condensation build-up due to poor ventilation. Recommend a qualified contractor evaluate further to repair or replace as needed.
Ventilation may have been insufficient at the time of the inspection.
Inadequate attic ventilation can cause the attic to overheat, causing heat damage to the roof covering, which results in a decreased life expectancy. Adequate ventilation of the attic will actually help prolong the life expectancy of the roof covering and help stabilize interior temperatures when heating and cooling is in use.
Recommend a qualified contractor evaluate to ensure all attic ventilation is unobstructed and fully functional and/or install additional ventilation as needed.



An exterior light fixture or light was missing it’s cover. A qualified contractor should evaluate and repair or replace as necessary according to current standards.


The outside water faucet had a significant leak from the knob/handle when the water pressure gauge was attached. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

Cracked or split boards were present at the deck. This condition is a structural defect and potential safety hazard.
A qualified contractor should evaluate and repair or replace as necessary.

Flashing was missing at the ledger board. This flashing problem may allow water to enter into the wall cavity or building components. A qualified contractor should evaluate and repair or replace as necessary.

The guard/hand rail had horizontal railings. This creates a climbing risk and a fall or injury could occur if not corrected. A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.


Downspout(s) are missing the proper 6 ft. extensions. This condition may cause problems by introducing excessive amounts of moisture to the soil beneath the foundation. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

The inspector was unable to verify that the door was fire rated . This may be considered a fire safety hazard. The door between the garage and the house should be a solid wood door at least 1-3/8 inches thick, a solid or honeycomb-core steel door at least 1-3/8 inches thick, or a 20-minute fire-rated door. This means that should a fire occur in garage, the occupant door does not afford protection until firemen arrive. A qualified contractor should evaluate and repair or replace as necessary.

The door between the garage and the living space failed to close by itself. Modern safety requirements require that the door between the home interior and the garage be self-closing for safety reasons related to fire hazard and toxic fumes. A qualified contractor should evaluate and repair or replace as necessary.

The garage floor had surface spalling in areas. This condition will continue to degrade if not corrected. A qualified contractor should evaluate and repair or replace as necessary.




There appeared to be some damage to the interior flooring in areas. Recommend a qualified contractor evaluate and repair or replace as needed.

The floors showed signs of minor damage and wear, particularly in high-traffic areas. A qualified contractor should evaluate and repair or replace as necessary.

The door had a damaged or missing doorstop. A qualified contractor should evaluate and repair or replace as necessary.
The window appeared to have a broken seal that has been compromised. Condensation and/or cloudiness between the two panes of glass was observed. This will have a negative impact on energy efficiency. Also, because there is moisture between the panes with no ventilation, mold can eventually develop. A qualified contractor should evaluate and repair or replace as necessary.
Some windows had damaged or missing screens. A qualified contractor should evaluate and repair or replace as necessary.

At the interior stairs, the handrail had a railing end that did not return to the wall or post. A fall could occur if something (purse, backpack etc.) caught the end of the railing when descending. A fall or injury could occur if not corrected. A qualified contractor should evaluate and repair or replace as necessary.
Carbon monoxide detectors were not installed within a specified distance of each room lawfully used for sleeping purposes. The inspector recommends installation of carbon monoxide detectors in appropriate locations. Colorado House bill 1091 became effective on July 1, 2009 that requires Carbon Monoxide detectors to be installed in most properties that has a fuel-burning heater or appliance, a fireplace, or an attached garage.
There are no carbon monoxide detectors on the lower or upper level.

The counter top needs caulking with silicone along the back splash. A qualified contractor should evaluate and repair or replace as necessary.

Counters or cabinetry had a finish that was worn or peeling. Recommend a qualified contractor evaluate and repair or replace as needed.

The window had a crank handle that was damaged or not working properly. A qualified contractor should evaluate and repair or replace as necessary.

A cook top element was not working at the time of inspection. A qualified contractor should evaluate and repair or replace as necessary.
There was no ventilation (exhaust fan or openable window) In the laundry area. Normally an exhaust fan or an openable window is needed for proper ventilation. A qualified contractor should evaluate and repair or replace as necessary.
An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

The bathroom exhaust fan was weak. A qualified contractor should evaluate and repair or replace as necessary.


The tile floor had missing or damaged grout. A qualified contractor should evaluate and repair or replace as necessary.

The counter top needs caulking with silicone along the back splash. A qualified contractor should evaluate and repair or replace as necessary.

The tub/shower area had deteriorated or missing sealant (caulking or grout) at the corners and/or floor. Sealant is needed at wall corners inside the shower, corners from tub to wall, and along the floor perimeter. A qualified contractor should evaluate and repair or replace as necessary.

The counter top needs caulking with silicone along the back splash. A qualified contractor should evaluate and repair or replace as necessary.
The toilet continually “runs” after flushing. This generally means the interior tank components are not working properly. A qualified contractor should evaluate and repair or replace as necessary.

The tub/shower area had deteriorated or missing sealant (caulking or grout) at the corners and/or floor. Sealant is needed at wall corners inside the shower, corners from tub to wall, and along the floor perimeter. A qualified contractor should evaluate and repair or replace as necessary.

The property water supply pressure was measured at the exterior faucet or laundry hose bib. Property water supply pressure was lower than the 40 pounds per square inch (PSI), which is considered inadequate by generally-accepted current standards.
A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

The circuit labels were missing, partial, or illegible at the electrical distribution panel. The circuit labels provide information describing the locations each individual circuit breaker provides power too.
Recommend a qualified contractor verify the breakers and accuracy of any existing labeling as necessary.

The manufacturer’s label was missing, partial, or illegible at the electrical service panel. The manufacturer’s label typically provides information describing the main panel such as the name of the panel manufacturer, the panel model number, the panel amperage rating, limitations related to the environment in which the panel was designed to be installed and grounding/bonding information for that particular model. The Inspector was unable to confirm the existence of proper conditions when confirmation would require information taken from this missing label.



The service drop did not meet minimum clearances which is a major electrical hazard. Correction and further evaluation is recommended.
In general, a service drop must be at least:
- 2 feet above the immediate roof decking
- 3 feet away from an openable window or door
- 10 feet above areas accessible only to pedestrians, such as porches or decks
- 12 feet above the ground (grade) as well as sidewalks and residential driveway
- 22 1/2 feet above a swimming pool


The connection to the expansion tank was corroded at the time of the inspection
The combustion air supply for this appliance was not present. A qualified contractor should evaluate and make necessary corrections according to current standards.
Fresh air supply is recommended by manufacturers for efficient operation of fuel burning appliances. Years ago, the air could come from inside or outside the building, however, more recent standards prefer for combustion air to come from the outside only.

The water temperature was below the suggested range of 120-130 degrees. Recommend adjusting the water heater thermostat first. If water does not reach the acceptable range then a qualified contractor should evaluate and repair or replace as necessary.

Due to the year of manufacture, the heating system is assumed to be near the end of its expected service life. Regular maintenance and monitoring of its condition is recommended. Budgeting for repairs and future replacement is recommended. A qualified contractor should evaluate and repair or replace as necessary. InterNACHI’s Standard Estimate Life Expectancy Chart for Homes