3 – Attic, Insulation, and Ventilation
3.4.1 – Insulation in Attic
Insulation in Attic 1
COMPRESSED – INSULATION

The insulation had been walked on or had stored items compressing it, which reduces the R-value.

Recommend a qualified contractor to evaluate and repair or replace as needed.

3.4.2 – Insulation in Attic
Insulation in Attic 2
TOO THIN

The insulation is thinner than current thermal resistance (R-value) standards.

Recommend a qualified contractor to evaluate and repair or replace as needed.

 4 – Exterior – Condo/Townhome
4.1.1 – Exterior Doors

Exterior Doors 1

WEATHERED – DOOR

An exterior door is weathered or deteriorated. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

4.1.2 – Exterior Doors
Exterior Doors 2
LIGHT NOT WORKING

The entry light to the left of the front door was not working at the time of the inspection or possibly on a building timer.

 5 – Attached Garage
5.3.1 – Ceiling, Walls & Firewalls
Ceiling, Walls & Firewalls 1
DAMAGE – CEILING
MINE ARE CRACKING AND PULLING TAPE GARAGE

The ceiling in the garage was damaged.

Recommend a qualified contractor to evaluate and repair or replace as needed.

5.3.2 – Ceiling, Walls & Firewalls

Ceiling, Walls & Firewalls 2

DAMAGE – WALL
GARAGE

An interior wall in the garage was damaged.

Recommend a qualified contractor to evaluate and repair or replace as needed.

5.3.3 – Ceiling, Walls & Firewalls
Ceiling, Walls & Firewalls 3
SIGNS OF REPAIRS

Walls and/or ceilings had signs of repairs at the time of inspection. Recommend asking current homeowners for more information. Should repairs appear to be poorly done, we recommend having a qualified contractor evaluate further for any further repairs.

5.4.1 – Floor
Floor 1
Floor 2
Floor 3
CRACKING – COMMON

The concrete floor in the garage was cracked. Due to expansive soils, minor cracks are to be expected in the slabs or control joints. Recommend a qualified contractor to evaluate and repair or replace as needed.

5.6.1 – Door Opener
Door Opener 1
NOT WORKING – LIGHT BULB

The garage door opener had a light bulb that was not working. Recommend a qualified contractor to evaluate and repair or replace as needed.

 6 – Interior, Doors, Windows
6.2.1 – Ceilings & Walls
Ceilings & Walls 1
CRACKING AROUND WINDOW

There was cracking around some windows on the interior (where the window meets the wall).  A qualified contractor should evaluate and repair or replace as necessary.

6.2.2 – Ceilings & Walls

Ceilings & Walls 2

MINOR CRACKS-CEILING

Minor cracking was visible on the interior ceilings.  A qualified contractor should evaluate and repair or replace as necessary.

6.2.3 – Ceilings & Walls

Ceilings & Walls 3

Ceilings & Walls 4

SIGNS OF REPAIR-CEILINGS

The interior ceilings have signs of repairs. Recommend asking the current homeowner for more information. Recommend further evaluation from a qualified contractor should the repairs be excessive or of visibly poor quality.

6.3.1 – Floors

Floors 1

MISSING/DAMAGED GROUT

The tile floor had missing or damaged grout.  A qualified contractor should evaluate and repair or replace as necessary.

6.3.2 – Floors
Floors 2
WEAR AND TEAR
THROUGHOUT PROPERTY

The floors showed signs of minor damage and wear, particularly in high-traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

6.5.1 – Windows

Windows 1

Windows 1

SPRING RAIL LOOSE

The window had spring rails that are loose and the window doesn’t operate properly.  A qualified contractor should evaluate and repair or replace as necessary.

6.6.1 – Electrical Outlets

Electrical Outlets 1

NOT GROUNDED – OUTLET

One or more electrical outlets were not grounded. A qualified contractor should evaluate and repair or replace as necessary.

6.12.1 – Installed Heat Source 2
Installed Heat Source 2 1
LOOSE, DAMAGED – REGISTER COVER
GUEST BEDROOM

The supply register cover was loose or damaged.  A qualified contractor should evaluate and repair or replace as necessary.

6.13.1 – Fireplaces Gas/LP
Fireplaces Gas/LP 1
FIREPLACE – DIRTY

Excessive lint, dust, and/or debris were built up in the pilot ignition compartment. Recommend further evaluation and proper cleaning by a qualified professional.

 7 – Kitchen
7.3.1 – Ceilings & Walls

Ceilings & Walls 1

MISSING – BASEBOARD TRIM

Baseboard trim was missing in areas of the interior walls at the time of inspection. A qualified contractor should evaluate and repair or replace as needed.

7.4.1 – Floors
Floors 1
MISSING TRANSITION PIECE

A transition piece was missing between two sections of flooring.  A qualified contractor should evaluate and repair or replace as necessary.

7.5.1 – Cabinets & Counters
Cabinets & Counters 2
CAULKING – BACKSPLASH

The countertop needs caulking with silicone along the backsplash.  A qualified contractor should evaluate and repair or replace as necessary.

7.5.2 – Cabinets & Counters
Cabinets & Counters 3
WORN FINISH

Counters or cabinetry had a finish that was worn or peeling. Recommend a qualified contractor to evaluate and repair or replace as needed.

7.17.1 – Refrigerator
Refrigerator 1
NOT COOLING PROPERLY

The refrigerator/freezer was not cooling at proper temperatures.  It is recommended that a refrigerator cools at around 38 degrees while a freezer cools at around zero degrees.  A qualified contractor should evaluate and repair or replace as necessary.

 8 – Laundry
8.4.1 – Exhaust Fan
Exhaust Fan 1
LOOSE
LAUNDRY AREA

The laundry area exhaust fan was loose.  A qualified contractor should evaluate and repair or replace as necessary.

8.5.1 – Ceilings & Walls

Ceilings & Walls 1

ACCESS HOLE

The drywall was cut out for an access hole.  A qualified contractor should evaluate and repair or replace as necessary.

8.8.1 – Floors
Floors 1
WEAR AND TEAR

The floors showed signs of minor damage and wear – particularly in high-traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

8.8.2 – Floors

Floors 2

FLOOR DAMAGED

There appeared to be some damage to the interior flooring in areas. Recommend a qualified contractor to evaluate and repair or replace as needed.

8.9.1 – Electrical Outlets
Electrical Outlets 1
GFCI PROTECTION IS NOT PRESENT
LAUNDRY AREA

An outlet did not provide Ground Fault Circuit Interrupter (GFCI) protection. Although GFCI protection of circuits may not have been required at the time in which this home was built, safe building practices have improved with the passage of time and building standards have changed to reflect current understanding. The inspector recommends updating the existing electrical circuits to include GFCI protection. A qualified contractor should evaluate and repair or replace as necessary.

 9 – Bathroom
9.3.1 – Exhaust Fan

Bathroom Exhaust Fan 1

LOOSE

The bathroom exhaust fan was loose and/or hanging.  A qualified contractor should evaluate and repair or replace as necessary.

9.5.1 – Floors

Floors 1

WEAR AND TEAR

The floors showed signs of minor damage and wear – particularly in high-traffic areas.  A qualified contractor should evaluate and repair or replace as necessary.

9.12.1 – Plumbing Fixtures

Plumbing Fixtures 1

MISSING – TRIM PIECE

The shower/bathtub was missing a trim piece.  A qualified contractor should evaluate and repair or replace as necessary.

9.14.1 – Tub, Shower Area

Tub, Shower Area 1

CAULK – SPOUT/LEVER

The tub spout and or control lever cover plate was missing silicone caulking.  A qualified contractor should evaluate and repair or replace as necessary.

 10 – Bathroom 2
10.3.1 – Exhaust Fan
Bathroom 2Exhaust Fan 1
NOT WORKING
PRIMARY

The bathroom exhaust fan did not work.  A qualified contractor should evaluate and repair or replace as necessary.

10.4.1 – Ceilings & Walls

Ceilings & Walls 1

SIGNS OF REPAIR-WALLS

The walls had signs of a previous repair.  A qualified contractor should evaluate and repair or replace as necessary.

10.5.1 – Floors

Floors 1

CARPET LOSE

The carpet was loose or baggy and may need to be restretched.  A qualified contractor should evaluate and repair or replace as necessary.

10.5.2 – Floors
Floors 2
MISSING TRANSITION PIECE

A transition piece was missing between two sections of flooring.  A qualified contractor should evaluate and repair or replace as necessary.

10.7.1 – Electrical Outlets

Electrical Outlets 1

LOOSE – OUTLET

An electrical outlet was loose in the wall. A qualified contractor should evaluate and repair or replace as necessary.

10.10.1 – Drain Waste and Vent System
Drain Waste and Vent System 1
NOT WORKING – SINK STOPPER
PRIMARY

The drain stop did not work or did not hold water in the sink.  A qualified contractor should evaluate and repair or replace as necessary.

10.14.1 – Tub, Shower Area

Tub, Shower Area 1

Tub, Shower Area 2
CAULK – CORNERS AND FLOOR

The tub/shower area had deteriorated or missing sealant (caulking or grout) at the corners and/or floor. Sealant is needed at wall corners inside the shower, corners from tub to wall, and along the floor perimeter.  A qualified contractor should evaluate and repair or replace as necessary.

 11 – Electrical
11.5.1 – Electrical Circuit Breakers

Electrical Circuit Breakers 1

DIFFERENT BRANDS

Some or all circuit breakers were a brand different from the main panel brand. Circuit breakers made by different manufacturers vary in design, therefore panel manufacturers require their own manufactured breakers to be used. Select brands are interchangeable, and there are some “semi” universal breaker types or panel types.

Using incompatible breakers in the panel of another manufacturer may result in poor connections which can create a potential fire or shock/electrocution hazard. A qualified contractor should evaluate and repair or replace as necessary.

 13 – Water Heating Equipment
13.4.1 – Expansion Tank / Valve
Expansion Tank / Valve 1
NOT SECURED

The expansion tank was not properly secured. A qualified contractor should evaluate and repair or replace as necessary.

13.8.1 – Temperature & Pressure Relief Valve
Temperature & Pressure Relief Valve 1
OVER 6″ FROM FLOOR

The TPRV pipe did not conspicuously terminate within 6 inches of the floor. This may allow high-pressure hot water to cause unnecessary damage. A qualified contractor should evaluate and repair or replace as necessary.

 14 – Cooling
14.3.1 – AC Compressor
AC Compressor 1
UNIT IS NOT LEVEL

The exterior compressor unit was not level. Over time, this may result in noisy fan operation, damage to the fan bearings, and a shortened fan lifespan, or it may result in movement of the compressor housing which can cause leaks in refrigerant lines resulting in expensive service. A qualified contractor should evaluate and repair or replace as necessary and according to current standards.

 15 – Heating
15.1.1 – Heating System Information
SERVICING RECOMMENDED

Based on the age of the heating system it is recommended that it be cleaned and serviced and certified (if possible) by an HVAC professional.

15.6.1 – Cabinet
Cabinet 1
CONDENSATION LEAK
MINOR PREVIOUS LEAK

The furnace cabinet interior at the blower chamber had moisture damage from a condensation leak. A qualified contractor should evaluate and repair or replace as necessary.